5.18
Programming:
To display the programming parameters, select
(menu) and the following will
be displayed progressively:
UP - User settings: these are the basic settings that the user can change.
AP - Advanced settings: these settings are available only to qualified
personnel. Password entry is required (contact PumpAssist for
assistance).
SA - Technical assistance settings: these are the advanced parameters, only
technical assistance personnel are allowed to access this menu.
Password entry is required (contact PumpAssist for assistance).
MAn - Fixed speed mode activation: this allows activation of the fixed speed
mode and the working frequency. Only qualified personnel are allowed to
access this menu. Password entry is required (contact PumpAssist for
assistance).
AE - Advanced parameters: this allows display of the secondary parameters
which can be useful for system diagnostics.
Example: AE01 software release
AE02 supply voltage (V)
AE03 last 5 faults
5.19
Supply voltage display:
By pushing the
button (menu) the UP parameter appears. Select the AE
parameter by pushing the
(plus) up to arrive at the correct parameter
, confirm with
(enter).
Select the parameter
by pushing the button
(plus) and confirm with
(enter).
Supply voltage is displayed.
5.20
UP - User settings
UP01-04 are factory set and should not be changed.
No
Description
Factory
settings
Modifications
Note
UP01
restart mode power failure
[rA = automatic; rM = manual]
rA
UP02
Nominal pump current
(A)
0.1
UP03
Nominal pump frequency
(HZ)
50
UP04
Direction of rotation
[--- = std rotation; E--- = inverted rotation]
---
UP05
Set point pressure
(bar)
1.5
E
E