- 11 -
Cont ...
4.19
Wiring Diagram:
Connect the pump set to the supply in accordance with the wiring diagram
shown below.
E
N
E
L
VSD
1
L1
U
N
V
PE
PE
1
4
5
2
6
10
8
11
9
3
1
8
9
10
11
L1
N
U
V
PE
PE
4
1
5
2
6
8
10
9
11
1
3
240v/1ph/50Hz/N/E
25 Amp Supply
63A/AC1
Panel Isolator
2.5 mm2 Tri-Rated
MS-HBC aM
P1
F
AquaBoost Controller
Pump
Pressure
Transducer
Float Switch
Closes to
Stop pump
Break Tank
(Optional)
Fault
Indication
Remote
(Optional)
MS-HBC aM
AquaBoost Controller
Pump
VSD2
Pressure
Transducer
Aquaboost Booster Set range
Fig. 5
Note:
This switch does not isolate
all connections to this panel.
Isolate elsewhere before
working on this equipment
Note:
1. This panel must be protected by a Type D
M.C.B or motor rated BS88 fuse, rating
see Section 3.21.
2. All protective devices are set to manual reset.
3. Panel wiring: All cables are Tri-rated
Mains=Phase Bm/Blk/Gry 2.5 mm
2
Motors=Phase Bm/Blk/Gry 1.5 mm
2
240 V a.c. Live=Brown/Neutral=Blue 0.5 mm
2
DC Live=Red/Neutral=Blue 0.5 mm
2
Volt free=White 0.5 mm
2
4. Earth Bonding=G/Y 4.0 mm
2