ELECTRICAL INSTALLATION
•
Regulations
: The electrical installation must be carried out in
accordance with the current national electrical regulations and
installed by a qualified person.
•
Safety
: In the interests of electrical safety a 30 mA residual
current device (
R.C.D. not supplied
) should be installed in the
supply circuit. This may be part of a consumer unit or a separate
unit.
•
Before starting work on the electrical supply ensure power
supply is isolated.
•
DO NOT
allow the supply cord to contact hot surfaces, including
the motor shell, pump body or pipework. The cord should be
safely routed and secured by cable clips.
•
Adjacent pipes
: Adjacent suction and delivery pipes should be
fitted with earthing clamps and connected with earthing wire
size 4 mm
2
Figure 12
Earth continuity connections
•
Earthing
: This appliance must be earthed via the supply cord,
which must be correctly connected to the earth point located in
the terminal box.
•
Pipework
: Copper or metallic pipework must have
supplementary earth bonding where the continuity has been
broken by flexible hoses or plastic components.
•
Additional earthing
: Certain installations may require additional
earthing arrangements such as equipotential bonding. Reference
should be made to the relevant regulations concerning this
subject to ensure compliance.