4. CHIMNEY 

Chimney of appropriate height and diameter is very important for proper operation of boiler. Before connecting the 
boiler to the chimney, check if its flue is suitable (diameter of flue must be not lower than of boiler’s flue), if there are 
other systems connected to the chimney. Chimney must be installed according to current standards and regulations. 
Chimney’s draft must be 20-25 Pa. If draft is low, boiler will operate poorly (buildup of resins, congestion, smoking) and 
it‘s service life will be shorter. 

NOTE 

In order to prevent chimney’s performance deterioration, caused by rain water steam and buildup of 
resin, it must be impermeable and isolated. 

 

In case of excessive draft, there will be increase in fuel consumption and in extreme cases there is a chance of 
overheating the device. This flaw can be eliminated by installing draft limiter. Chimney sweep must assess the technical 
condition of chimney which will be connected to boiler. In order to safeguard the system form wind gusts, chimney 
must rise no less than one meter above the roof. Premise, in which the boiler will be installed, must meet the 
requirements of “the rules of installing solid fuels boilers in buildings ST 8860237.02:1998”. 

Chimney must meet specific regulations, of the country where it is being installed. 

Lowest dimensions of flue recommended by manufacturer of boiler: 

 

Round cross-section – 150 mm 

 

Square cross-section – 140 x 140 mm 

Boiler‘s flue must be connected to chimney’s steel part of suitable size and form.  

Connection must be leak-proof. 

 

 

 

 

 

 

 

 

 

Содержание Pellet boiler Series

Страница 1: ...Pellet boiler TECHNICAL PASSPORT INSTALLATION AND MAINTENANCE MANUAL...

Страница 2: ...ghest pressure of heat transfer medium is 0 15 MPa Integral part of boiler Granulinis is electronic control block Company reserves the right to change the construction and assures that these changes w...

Страница 3: ...ng other manufacturer s parts __________________________________________________________________________________________________ DANGER Danger of poisoning with carbon monoxide If boiler uses air from...

Страница 4: ...ler when it is working Boiler s operating temperature must not exceed 85 o C it must be constantly observed It is forbidden to use liquids for ignition of fire or to increase the power of boiler Remov...

Страница 5: ...wood oak wood panels HOBREX VERZALIT Formica C2 average flammability Wood of pine larch and spruce also products covered with such wood C2 flammable Asphalt cardboard cellulose materials bituminized p...

Страница 6: ...nd water column is larger than 15 m spiral cooler with permeability of 1500 l h needs to be installed Pressure of cold water supplied to safety device cannot be lower than 2 bar Water flow from cooler...

Страница 7: ...d in rated data plate Parts of pellet boiler 1 Decoration of boiler 2 Burner of pellets 3 Pipe of heated water 4 Pipe of returning water 5 Heat exchanger with flowing water inside of it 6 Thermal insu...

Страница 8: ...ntact thermostat installed on piping fed by boiler For controlling temperature of outgoing water and for controlling the fan Airflow regulator 3 installed in burner Secondary air supply in into burnin...

Страница 9: ...00 1300 Standard load of fuel kg 30 60 90 Weight kg 82 87 92 Fuel consumption at rated power Kg h 4 0 4 0 4 0 Required chimney draft Pa 20 25 20 25 20 25 Power supply 230 V 6 A 230 V 6 A 230 V 6 A Max...

Страница 10: ...ase of excessive draft there will be increase in fuel consumption and in extreme cases there is a chance of overheating the device This flaw can be eliminated by installing draft limiter Chimney sweep...

Страница 11: ...vice need 230 V power supply therefore installation works must be carried out by a person with appropriate knowledge skills and who meets additional requirements of Country in which the boiler is inst...

Страница 12: ...lete manner 45 degrees When closing the pellets close the door If is not burning repeat After burning the burner after half an hour observe the smoke from the chimney if the smoke is dark it is too li...

Страница 13: ...roximately say 25 C T If the boiler thermostat switches off the burner to the remaining room before the required level set the temperature higher to 2 3 C If there is not enough heat in the room incre...

Страница 14: ...r will not be used for longer period of time for example when heating season is over use up all the fuel from the bunker Heat exchange medium mustn t be removed from the heating system before the down...

Страница 15: ...chimney because chimney s condition must be thoroughly inspected all damage must be repaired Also user needs to get permission from competent administration institutions to continue to use the chimne...

Страница 16: ......

Страница 17: ......

Страница 18: ...the requirements of Country in which it is operated Also follow these instructions when using the boiler 1 These actions have to be carried out before doing any maintenance work a Turn of the fan or...

Страница 19: ...ightness was inspected and it was confirmed as effective and suitable for use 1 If user follows the instructions of installation operation and maintenances indicated in user manual distributor provide...

Страница 20: ...stributor informs the manufacturer or user fills out request and after filling out a complaint provides a copy of document proving the purchase of product If passport of device is lost user is respons...

Страница 21: ...s product I believe that shortcoming listed in complaint were caused by defects of your product I ask you to send your representatives to inspect the connected device to determine and remove the defec...

Страница 22: ...ure of device copy of this passport is sent to seller or distributor Original copy of passport must be presented to authorized technician who comes to repair the failure Model Serial No Rated power Pu...

Отзывы: