AirSense Technology Ltd. 2005
Page 40
Stratos-Micra 100
• INSTALLER’S HANDBOOK • Iss. 3
13. Stratos-Micra 100
specification
SELV rating (EN 60950)
Class III
Supply Voltage
21.6V - 26.4V DC
PSU Type: conforming to EN 54-4
Electrical safety complies with BS EN
610190-1
Size (mm)
300W x 220H x 90D
Weight
3.8kg with docking station
Operating temperature range
0 to +38°C (UL268)
–10 to +60°C (CEA4022)
Operating humidity range
0 - 90% Non Condensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation Cat. II
Sensitivity range (%Obs/m)
Min = 25% Max = 0.03% FSD
Maximum sensitivity resolution
0.0015 % obs/m
Detection principle
Laser light scattering mass detection
Particle sensitivity range
0.0003µm to 10µm
Current consumption
400mA
Relay contact rating
500mA @ 30V
Maximum sampling pipe length
100 metres total (see design limitations
on section 5)
Sampling pipe inlets
2
Sampling pipe internal diameter
15-25mm
Alarm levels
4 (Fire 2, Fire 1, Pre-Alarm and Aux)
1 relay as standard, others available
Chamber service intervals
Greater than 8 years (depending on
environment)
Dust separator replacement intervals
Greater than 5 years (depending on
environment)
Laser lifetime (MTTF)
Greater than 1000 years
Programming
PC via RS232/RS485
Data bus cable
RS485 data cable
Data bus length
1.2 km
IP rating
IP50
This equipment is only to be used in accordance with this specification. Failure to
operate the equipment as specified may cause damage to the unit.
NB
+