Order no. 900340.012
V1.54
Page 18
The number of switching cycles is calculated as follows (i.e. for K1):
number =
65536 * N1 + N0
.
Parameter N98 resets the counters for all relays. It depends on the setting of parameter L42. The return value is
set back to “0” automatically.
T-level (operating times)
Parameters are only accessible via ST-Bus.
Para-
meter
Description of function
Setting range
Values
default
T10
Overall operating time (lower 16bit)
---
T11
Overall operating time (upper 16bit)
---
T12
Operating time since last reset (lower 16bit)
---
T13
Operating time since last reset (upper 16bit)
---
T14
Operating time relay “compressor” (lower 16bit)
---
T15
Operating time relay “compressor” (upper 16bit)
---
T16
Operating time relay “defrosting 1” (lower 16bit)
---
T17
Operating time relay “defrosting 1” (upper 16bit)
---
T18
Operating time relay “evaporator fan” (lower 16bit)
---
T19
Operating time relay “evaporator fan” (upper 16bit)
---
T20
Operating time relay “condenser fan” (lower 16bit)
---
T21
Operating time relay “condenser fan” (upper 16bit)
---
T22
Operating time relay “thermostat 2” (lower 16bit)
---
T23
Operating time relay “thermostat 2” (upper 16bit)
---
T24
Operating time relay “defrosting 2” (lower 16bit)
---
T25
Operating time relay “defrosting 2” (upper 16bit)
---
T26
Operating time relay “drip tray heating” (lower 16bit)
---
T27
Operating time relay “drip tray heating (upper 16bit)
---
T28
Operating time relay - (lower 16bit)
---
T29
Operating time relay - (upper 16bit)
---
T98
Reset operating times
0: ---
1: Reset
0
T99
Password for T-level
-99 … 999
0
The operating time is calculated as follows:
Operating time (in minutes) =
65536 * T11 + T10
.
Parameter T98 resets the counters for all operating times (except for T10 und T11). It depends on the setting of
parameter L42. The return value is set back to “0” automatically
EC-level (reserved for internal use)
This level is only accessible via ST-Bus.