Order no. 900340.012
V1.54
Page 26
Display value
Here, you can define which actual value is to be
displayed. This refers to the display in normal
operation. You will have to leave the parameter level in
order to see the set value.
Possible values which can be set via this parameter:
Description
0 Cold store temperature, frozen during
defrosting
1 Cold store temperature
2 Evaporator temperature
3 Current setpoint for evaporator fan
4 Current setpoint cold store, circuit 1
5 Condenser temperature (pressure?)
6 P-control result for condenser fan
7 Current setpoint for condenser fan
8 current setpoint of condenser
9 Cold store temperature via test bottle
function
10 MIN value of cold store temperature since
last reset
11 MAX value of cold store temperature since
last reset
12 Act. value control circuit 2
13 Current setpoint control circuit 2
14 Time
15 Date
Software version
Here, the software version of the controller is
displayed.
Display in standby mode
In this parameter, you can define what is to be
displayed in standby.
Mask on enabled functions (Bit 0...7)
Mask on enabled functions (Bit8...15)
Here, you can specify the functions enabled via the
bus using a binary mask. The bits have the following
meaning:
Para
Bit
Valency
Function
0 1
controller on/off
1 2
control circuit 1 on/off
2 4
control circuit 2 on/off
3 8
Control circuit 1:
defrosting request
4 16
Control circuit 1:
super-frost request
5 32
Control circuit 1: reserved
Para
Bit
Valency
Function
6 64
Control circuit 1:
Set1 / Set2 change-over
7 128
Control circuit 1:
day / night change-over
8 1
Control circuit 2:
defrosting request
9 2
Function A: light 1
10 4
Function B: light 2
11 8
Function C: window heating
12 16
Function D: door frame
heating
13 32
Function E: blade scraper
14 64
Function F: reserved
15 128
reserved
To determine the value to be parameterised, all
valencies must be added up.
Release for a deletion of the counter/runtimes
Here, the deleting of the runtimes, the relay counter
and the min/max memory will be released for 10
minutes. Only within these 10 minutes, can the
parameters T98, N98 and A17 actively delete the
corresponding timers, counters, or memory locations.
After the 10 minutes, the release will be removed. The
deletion of the min / max memory through a but-ton
function assignment will not be affect-ed by this.
Password for parameter level
With this parameter, you can set the password for
parameter level
.