Order no. 900340.012
V1.54
Page 10
Para-
meter
Description of function
Setting range
Values
default
Setpoint for Set1
...
0.0
Night setpoint
(relative to current setpoint
/
)
-20 ... +20.0°C
5.0
Setpoint for Set2
...
2.0
Switching mode
0: heating
1: refrigerating
1
Hysteresis
0.1...15.0°C
2.0
Hysteresis mode
0: symmetrical
1: one-sided
1
Upper setpoint limit
...+99°C
50.0
Lower setpoint limit
-99°C...
-50.0
Start protection after compressor start
0 ... 900 sec.
300
Start protection after compressor stop
0 ... 900 sec.
180
Start protection compressor after mains on
0 ... 60 min.
0
On-time in emergency operation
0 ... 100%
50
Cycle time in emergency operation
5 ... 60 min.
10
Assignment of sensor for "super-frost"
(also core or product temperature)
detailed description of sensors in parameters
through
0:none
1:Sensor F1
2:Sensor F2
3:Sensor F3
4:Sensor F4
5:weighted mean value from F1 and F2
1
"super-frost“: time limit
("shock-frost", "max. cooling power")
1 ... 36 hrs.
10
"super-frost“: temperature limit
("shock-frost", "max. cooling power")
-40 ... 0°C
0.0
"super-frost“: automatic off
("shock-frost", "max. cooling power")
0: none, manual only
1: controlled by time
2: controlled by time or temperature
2
Password of parameter level c
-99 ... 999
0
Defrosting control circuit 1
Para-
meter
Description of function
Setting range
Values
default
Assignment of evaporation sensors
(defrosting sensors)
detailed description of sensors in parameters
through
0:none
1:Sensor F1
2:Sensor F2
3:Sensor F3
4:Sensor F4
5: weighted mean value from F1 and F2
2
Defrosting interval
0: no automatic defrosting
1...99 hrs.
8
Type of defrosting
0: no defrosting
1: compressor off only (circulating air)
2: electrical
3: with hot gas
2
Stop at defrosting temperature
0 ... +30.0°C
10.0
Defrosting time limitation
1...99 min.
30