Second control level (P parameters): 

 

Setting of control parameters 

Simultaneously pressing the UP and DOWN key for at least 4 seconds opens a parameter list 
containing control parameters. 
With the UP and DOWN keys the list can be scrolled in both directions. 
Pressing the SET key will give you the value of the respective parameter. Pressing also the UP or 
DOWN key at the same time the value can be adjusted. 
Return to the initial position takes place automatically, if no key is pressed for 60 seconds. 
 
 

Para-
meter 

Function description 

Adjustment range 

Standard 
setting 

Custom 
setting 

P0 

Actual measuring value 

 

P2 

Hysteresis contact K1 

0.1... 99.9 K 

1.0 K 

 

P4 

Control range limitation – 
minimum setpoint 

-99°C...P5 

-99°C 

 

P5 

Control range limitation – 
maximum setpoint 

P4...999°C 

999°C 

 

P6 

Actual value correction 

-20.0...+20.0 K 

0.0 K 

 

P19 

Key-lock 

0: no key-lock 
1: key-lock 

 

P30 

Lower alarm value 

-99 ... 999°C/K 

-99°C 

 

P31 

Upper alarm value 

-99 ... 999°C/K 

100°C 

 

P32 

Hysteresis alarm circuit 

0.1... 99.9 K 

1.0 K 

 

d0 

Defrosting interval 

1...99 hours 
0: no defrosting 

8 h 

 

d2 

Defrosting temperature 

-99 …999 °C 

10.0 °C 

 

d3 

Defrosting time limit 

1…99 min 
0: without time limit 

30 min 

 

Содержание 900321.003

Страница 1: ...binet It was specifically developed for direct switching at high per formances Given the high maximum electric load of 16A ohm and 6A inductive it can operate without cut out relay in many cases The c...

Страница 2: ......

Страница 3: ...essed the display indicates the actual value of the temperature Pressing the SET key the setpoint shows on the display If the setpoint is to be changed the SET key is to be kept pressed while adjustin...

Страница 4: ...o key is pressed for 60 seconds Para meter Function description Adjustment range Standard setting Custom setting P0 Actual measuring value P2 Hysteresis contact K1 0 1 99 9 K 1 0 K P4 Control range li...

Страница 5: ...ances or extremely long sensor lines The regulation measure value is increased or decreased by the here adjusted value P19 Key lock The key lock allows blocking of the control keys In locked condition...

Страница 6: ...mperature value is reached The defrosting time set with d3 nevertheless runs at the same time i e it functions as safety net to terminate the defrosting process in case the defrosting temperature is n...

Страница 7: ...t 1 cooling contact 2 function alarm K1 0 A3 Function of contact K1 at sensor error 0 relay off 1 relay on 0 A8 Display mode all parameter indications are presented in 0 1 K 0 integrals 1 decimals in...

Страница 8: ...re scale and display when in Standby Mode 0 Fahrenheit AUS 1 Celsius AUS 2 Fahrenheit OFF 3 Celsius OFF 1 A85 Function key A if available 0 no function 1 indicate actual value if A32 1 2 activate setp...

Страница 9: ...m is released if the temperature lies beyond them In the case of sensor error the alarm is activated independently of this adjustment see fig 3 4 at parameters P30 31 A31 Special function at boundary...

Страница 10: ...ameter can determine by how many measured values an average value is to be formed If a sensor with a very fast reaction to external influences is used an average value ensures a calm signal process A8...

Страница 11: ...lock active Change parameter P19 or A19 display flashes Temperature alarm at too high or too low temperature if activated see A31 Buzzer Temperature alarm at too high or too low temperature if activa...

Страница 12: ...conductive strips Display One 3 digit LED Display height 13 mm colour red 1 LED diameter 3mm colour red for status display of K1 Power supply 230V 50 60 Hz power consumption max 5 VA Connectors screw...

Отзывы: