SOFTWARE .10
Adjustment options
Key 1: UP
Pressing this key you can increase the parameter or parameter value or scroll the
parameter list.
Key 2: DOWN
Pressing this key you can decrease the parameter or parameter value or scroll the
parameter list. At alarm the buzzer function can be switched off with this key.
Key 4: SET
While SET key is pressed, the setpoint is indicated.
In addition, the SET key is used for setting parameters
Key 5: Standby
Switching the controller on or off.
First control level:
Parameter setting of the control setpoint
If none of the keys is pressed, the display indicates the actual value of the temperature. Pressing
the SET key, the setpoint shows on the display.
If the setpoint is to be changed, the SET key is to be kept pressed while adjusting the setpoint with
the keys UP and DOWN.
Please note that the setpoint can only be changed within the set setpoint limits.
With appropriate parameter settings (see A85, A86) a second setpoint S1’ can be activated with a
special key A or B (if available).
The setpoint S1’ can be adjusted in the same way. If setpoint S1’ is activated it is indicated and
relevant for the control.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
S1
Setpoint
P4...P5
0.0°C
S1‘
Setpoint S1’ (relative)
Setpoint S1’ (absolute)
-99...+99.9 K if A33=1
P4...P5, if A33=2
0.0°C/K