Parameter description: 

 

P2:  Hysteresis contact K1 

The hysteresis can be set symmetrically or one-sided at the setpoint (see A40, A41). 
At one-sided setting, the hysteresis works downward with heating contact and upward with cooling 
contact. At symmetrical hysteresis, half of the hysteresis’ value is effective below and half of the 
value above the switching point (see fig. 1 and 2). 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 1:

 Heating controller, one-sided hysteresis 

  

Fig. 2:

 Cooling controller, symmetrical 

hysteresis 

 
P4: Control range limitation – minimum setpoint 
P5: Control range limitation – maximum setpoint 

The adjustment range of the setpoint can be limited in both directions. This is to prevent the end 
user of a unit from setting inadmissible or dangerous setpoints. 

 
P6: Actual value correction 

This parameter allows the correction of actual value deviations caused for example by sensor 
tolerances or extremely long sensor lines. The regulation measure value is increased or decreased 
by the here adjusted value.  
 

P19: Key-lock 

The key-lock allows blocking of the control keys. In locked condition parameter adjustments with 
keys is not possible. At the attempt to adjust the parameters despite key-lock the message "===" 
appears in the display. 

 
P30: Lower alarm value 
P31: Upper alarm value 

The exit alarm is a boundary alarm or a range alarm with symmetrical hysteresis (see parameter 
P32). Both at the boundary alarm and the range alarm, limit values can be relative, i.e. going along 
with the setpoint, or absolute, i.e. independent of the setpoint. At boundary alarm the hysteresis 
works one-sided inwardly, and at range alarm outwardly. 

 
P32: Hysteresis alarm circuit 

Hysteresis is set one-sided at the adjusted limit value. It becomes effective depending on alarm 
definition. 
 

d0: Defrosting interval 

The "defrosting interval" defines the time, after which a defrosting process is started. After each 
defrosting start, this time is reset and runs the next interval. 
 

 
 
 

Содержание 900321.003

Страница 1: ...binet It was specifically developed for direct switching at high per formances Given the high maximum electric load of 16A ohm and 6A inductive it can operate without cut out relay in many cases The c...

Страница 2: ......

Страница 3: ...essed the display indicates the actual value of the temperature Pressing the SET key the setpoint shows on the display If the setpoint is to be changed the SET key is to be kept pressed while adjustin...

Страница 4: ...o key is pressed for 60 seconds Para meter Function description Adjustment range Standard setting Custom setting P0 Actual measuring value P2 Hysteresis contact K1 0 1 99 9 K 1 0 K P4 Control range li...

Страница 5: ...ances or extremely long sensor lines The regulation measure value is increased or decreased by the here adjusted value P19 Key lock The key lock allows blocking of the control keys In locked condition...

Страница 6: ...mperature value is reached The defrosting time set with d3 nevertheless runs at the same time i e it functions as safety net to terminate the defrosting process in case the defrosting temperature is n...

Страница 7: ...t 1 cooling contact 2 function alarm K1 0 A3 Function of contact K1 at sensor error 0 relay off 1 relay on 0 A8 Display mode all parameter indications are presented in 0 1 K 0 integrals 1 decimals in...

Страница 8: ...re scale and display when in Standby Mode 0 Fahrenheit AUS 1 Celsius AUS 2 Fahrenheit OFF 3 Celsius OFF 1 A85 Function key A if available 0 no function 1 indicate actual value if A32 1 2 activate setp...

Страница 9: ...m is released if the temperature lies beyond them In the case of sensor error the alarm is activated independently of this adjustment see fig 3 4 at parameters P30 31 A31 Special function at boundary...

Страница 10: ...ameter can determine by how many measured values an average value is to be formed If a sensor with a very fast reaction to external influences is used an average value ensures a calm signal process A8...

Страница 11: ...lock active Change parameter P19 or A19 display flashes Temperature alarm at too high or too low temperature if activated see A31 Buzzer Temperature alarm at too high or too low temperature if activa...

Страница 12: ...conductive strips Display One 3 digit LED Display height 13 mm colour red 1 LED diameter 3mm colour red for status display of K1 Power supply 230V 50 60 Hz power consumption max 5 VA Connectors screw...

Отзывы: