Status messages
Message
Cause
Error elimination
“AUS” or “OFF”
Standby modus, no regulation
Switch on with standby key
F1L
Sensor error,
short-circuit at sensor F1
Check sensor
F1H
Sensor error,
open-circuit at sensor F1
Check sensor
_ _ _
Key-lock active
Change parameter P19 or A19
display flashes
Temperature alarm at too high or too
low temperature (if activated) see A31
Buzzer
Temperature alarm at too high or too
low temperature (if activated) see A31
The buzzer function can be switched
off with the DOWN-key
EP, display
flashes
Data loss at parameter memory
(Contacts K1 and K2 are switched off)
If error cannot be eliminated by
switching on/off, the controller must be
repaired