Third control level (all parameters):
Setting of control parameters
Access to the third control level is granted when selecting parameter PA on the second control
level. Parameter PA is to be set at '
-19
'. Then the key UP and DOWN have to be simultaneously
pressed for approx. 4 seconds which will give access to the third control level, beginning with
parameter P0. With the keys UP and DOWN you can scroll the list in both directions. Pressing the
SET key will give you the value of the respective parameter. By pressing the UP or DOWN key at
the same time the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds.
Parameters for controller specifications
Para-
meter
Function Adjustment
range
Standard
setting
Customer
setting
P0
Indication of cold room
temperature (sensor F1)
N/A N/A
P1
Calibration sensor F1,
actual value correction
-9.9...9,9 K
0.0 K
P2
Indication of evaporator
temperature (sensor F2)
N/A N/A
P3
Calibration sensor F2,
actual value correction
-9.9...9.9 K
0.0 K
P4
Sensor type F1
1: KTY
2: PT1000
3: NTC
1
P5
Sensor type F2
0: inactive
1: KTY
2: PT1000
3: NTC
1
P6
Display mode cold room
temperature
0: with decimals
1: without decimals
0
P7
Temperature scale
0: Fahrenheit (50Hz)
1: Celsius (50Hz)
2: Fahrenheit (60Hz)
3: Celsius (60Hz)
1
Parameters for the cooling controller
Para-
meter
Function Adjustment
range
Standard
setting
Customer
setting
r0
Hysteresis for the
compressor contact
0.1...15 K
2 K
r1
Setpoint limitation
(minimum)
-99...r2°C
-50°C
r2
Setpoint limitation
(maximum)
r1...+99°C
50°C