Order No.: 199927 

Technical data of TRT252-31.34

 

 
Input 
E1: 

External potential-free switching input, function see parameter b0. 

 

Measuring input

 

F1:

 

Resistance thermometer PTC, counter temperature, plug colour white 

F2:

 

Resistance thermometer PTC, evaporator sensor, plug colour red 

 

Measuring range: -55 °C...+99°C 

F3:

  

Current input 0-20mA 

 

Measuring accuracy: 0.5 % of scale range, without sensor 

 

Outputs

 

S1:

 

Triac, 4A, 230V ( 0...100 % linear) 

 

with 4A T fuse, potential-free, ventilator 

K1:

 

Relay, 16A 250V, without fuse, see parameter U1 

K2:

 

Relay, 16A 250V, with 6.3A T fuse, see parameter U2 

K3:

 

Relay, 16A 250V, with 6.3A T fuse, see parameter U3 

K4:

 

Relay, 16A 250V, with 6.3A T fuse, see parameter U4 

K5:

 

Relay, 16A 250V, with 6.3A T fuse, see parameter U5 

Relays K1 up to K5 are potential-afflicted 
Additional buzzer, 85dB 
 

Display

 

One 3-digit LED-Display, height 13mm, for temperature display, colour red, including the switching 
condition display for the output relays 
One 4-digit LED-Display, height 13 mm, colour red, for internal real time clock 
8 LEDs, for status display 
 

LON communication interface 

shielded 2-wire line, Twisted Pair, 78kBaud, not polar, maximum cable length 100m 
Interface driver: FTT10A, galvanically separated. 
The network can be installed in arbitrary topology.  
 

Power supply

 

230V 50Hz, max. 10VA 
 

Ambient conditions:

 

Storage temperature:  

-20...+70°C 

Operating temperature: 

0...55°C 

Relative humidity: 

 

max. 75%, without dew 

 

Enclosure

 

Front IP63, IP00 from back 
 

Installation data

 

Unit is to be installed in an instrument panel. 
Front size:  

 

 

252 x 72 mm 

Panel cut-out:  

 

242.5 x 50.5 mm 

Installation depth: 

 

ca. 200 mm 

 

Содержание TRT252-31.34

Страница 1: ...possible to adapt the general functions and thus the gradient of the temperature in the refrigerator to the currently needed times Various parameters and an additional current and or switching input and a external satellite tem perature display permit employment of the most various tasks Contacts of all inputs and outputs are special plug in connectors They are unmistakably marked with coloured an...

Страница 2: ...Sensor PTC Range 55 99 C Front size 252mm x 72mm Panel cut out 243mm x 51mm Tightness front IP63 Connector plug and socket ...

Страница 3: ...sed for at least half a second The lamp in the display lights up if cooling is switched off and the unit is in standby mode Key StandBy With this key the controller is switched to standby mode Pressing the key a second time restarts the unit The LED lights up if the controller is in standby mode all other displays are switched off Switching on the unit activates the time display The condition of s...

Страница 4: ...th the keys UP and DOWN Please note that the setpoint can only be changed within the set setpoint limits The time can be adjusted with the SET time key in the same way General reference Note that the value is transferred to the captive memory and is safe also after power failure Para meter Function Adjustment range Standard setting Customer setting S1 Cold room setpoint S1 Please note during night...

Страница 5: ...P0 Indication of cold room temperature sensor F1 P2 Indication of evaporator temperature H00 actual weekday 1 Sunday 2 Monday 3 Tuesday 4 Wednesday 5 Thursday 6 Friday 7 Saturday H01 Defrost time 1 00 00 24 00 24 00 inactive 24 00 H02 Defrost time 2 00 00 24 00 24 00 inactive 24 00 H03 Defrost time 3 00 00 24 00 24 00 inactive 24 00 H04 Defrost time 4 00 00 24 00 24 00 inactive 24 00 H05 Defrost t...

Страница 6: ...defrost times of the real time clock are used the defrost interval parameter d0 should be set to 0 H6 Night time reduction H07 H20 Start and end times of night time reduction The night time reduction is activated by the clock according to the start and end times set with parameters H7 H20 During the reduction the parameter S1 is effective for the control S1 is the sum of S1 daytime setpoint and H6...

Страница 7: ... Parameters for controller specifications Para meter Function Adjustment range Standard setting Customer setting P0 Indication of cold room temperature sensor F1 N A N A P1 Calibration sensor F1 actual value correction 9 9 9 9 K 0 0 K P2 Indication of evaporator temperature sensor F2 N A N A P3 Calibration sensor F2 actual value correction 9 9 9 9 K 0 0 K P4 Sensor type F1 1 KTY 2 PT1000 3 NTC 1 P...

Страница 8: ...lectrical 1 with hot gas 0 d2 Defrosting temperature 55 99 C 10 C d3 Defrosting time limit 1 99 min 30 min d4 Function after cooling on 0 immediate cooling no defrost 1 first defrosting then cooling 0 d5 Defrost delay after cooling on 0 30 min 0 min d6 Indication of the cold room temperature during defrosting 0 actual temperature 1 temperature determined just before the start of defrosting 0 d7 Dr...

Страница 9: ...on Adjustment range Standard setting Customer setting F0 Ventilator control 0 dependent on temperature 1 continuous on 0 F1 Ventilator setpoint 99 99 C 1 C F2 Switching hysteresis ventilator 2 15 K 2 K F3 Behaviour at compressor stop 0 ventilator independent of compressor 1 ventilator off together with compressor 1 F4 Behaviour at defrosting 0 ventilator independent of defrosting 1 ventilator off ...

Страница 10: ...unction output K2 0 8 see U1 1 U3 Function output K3 0 8 see U1 2 U4 Function output K4 0 8 see U1 3 U5 Function output K5 0 8 see U1 4 U6 Function output K6 0 8 see U1 5 YA Activation 0 not active 1 0 20mA 2 4 20mA 0 Y0 Indication of actual value N A N A Y1 Setpoint Y6 Y7 0 Y2 Heating cooling 0 heating 1 cooling 0 Y3 Hysteresis 0 1 15K 1 Y4 Indication value 0 4mA 99 999 0 0 Y5 Indication value 20...

Страница 11: ...d above the setpoint r1 Setpoint limitation minimum r2 Setpoint limitation maximum These parameters limit the adjustment range of the setpoint S1 in order to avoid that the end user sets inadmissible values for the plant c0 Start protection of the compressor after cooling on After cooling is switched on e g by switching on the mains voltage the start of the compressor is retarded until the protect...

Страница 12: ...e defrosting is terminated even if the evaporator is not warm enough to be ice free d4 Function after cooling on After cooling on cooling can start immediately and defrosting starts after the defrost interval or defrosting can start immediately and then the defrost interval is started For deep freezing applications the immediate defrosting is recommended since a defrost cycle might be skipped in c...

Страница 13: ...efrost start can be realised The parameter dH pre vents the controllers from switching back from defrosting to cooling mode at different times If dH is set to 1 the starting of the compressor is delayed until the time d3 defrosting time limit expires dU start manual defrosting only required in combination with data logger With dU 1 the defrost interval is started prematurely The following automati...

Страница 14: ... night time reduction After each switching process of the night time reduction activation or deactivation the alarm is suppressed for this time period In general the ventilator is supposed to be connected to the evaporator and the corresponding temperatures are determined by the evaporator sensor F0 Ventilator control At setting 0 the control is dependent of temperature with the ventilator setpoin...

Страница 15: ...y of the evaporator F7 Ventilator revolution number during normal cooling operation F8 Ventilator revolution number during night time reduction F9 Ventilator revolution number during defrosting The ventilator speed can be set infinitely variable by the software In Off condition the ventilator speed is reduced to 0 Irrespective of this setting there is always a kick start for the ventilator i e it ...

Страница 16: ...ff 21 off with cooling off independent see left column off with cooling off 22 independent off with cooling off see left column off with cooling off 23 off with cooling off off with cooling off see left column off with cooling off 24 independent Adjusting Y1 like U parameter 8 independent 25 off with cooling off Adjusting Y1 like U parameter 8 independent 26 independent Adjusting Y1 like U paramet...

Страница 17: ...ss and subnet address with Domain 0 The address of the knot can only be changed if the knot was not tied externally SNVT nciNetConfig CFG_LOCAL otherwise the changed value is not saved after releasing the set key the old value is reset L2 Number of Slaves This is the number of slaves which have to receive a defrost demand via the network The slave addresses start with controller address L0 1 L9 Lo...

Страница 18: ...put Bit 0 compressor Bit 1 ventilator Bit 2 defrost Bit 3 alarm switching conditions nvoSwitch SNVT_lev_disc Output ST_OFF ST_ON reserved nviDayNight SNVT_lev_disc Input ST_OFF ST_ON external night time reduction nviCutoutTemp SNVT_temp_p Input 100 150 C setpoint nviDefrostState SNVT_defr_state Input DF_STANDBY DF_DEFROST defrost demand nviSwitch SNVT_lev_disc Input ST_OFF ST_ON reserved nviPower ...

Страница 19: ... be updated immediately if there is a change at the master controller If the setpoint is changed at the slave controller the correct value will be send to the slave after nciMaxSendTime seconds Connection information Simultaneously pressing all keys sends a Service Pin message the program version of the software is indicated in the display The controller responds to a wave command with a display f...

Страница 20: ...us only read D1 Bit 0 cooling on Bit 1 defrosting active Bit 2 night time reduction Bit 3 controller on Bit 4 compressor Bit 5 defrost relay Bit 6 light Bit 7 switching condition blue key Bit 8 switching condition red key Bit 9 ventilator on Bit 10 switching condition current input U parameter 7 Bit 11 switching condition current input U parameter 8 Bit 12 Switching input 1 Bit 13 Switching input ...

Страница 21: ...rs are indicated with a flashing display and the buzzer sounds If the display indicates a EP error the controller has located undesirable change of the parameter settings in the EEprom This indication can not be cancelled The controller has to be exchanged immediately In this case the compressor and the ventilator switch to emergency operation 15 min on 15 min off Common problems Setting of the ve...

Страница 22: ...ith 6 3A T fuse see parameter U5 Relays K1 up to K5 are potential afflicted Additional buzzer 85dB Display One 3 digit LED Display height 13mm for temperature display colour red including the switching condition display for the output relays One 4 digit LED Display height 13 mm colour red for internal real time clock 8 LEDs for status display LON communication interface shielded 2 wire line Twiste...

Отзывы: