First control level:
Adjusting the cold room setpoint and actual time
If none of the keys is pressed, the display indicates the actual value of the temperature and the
actual time. Pressing the SET key, the setpoint shows on the display.
If the setpoint is to be changed, the SET key is to be kept pressed while adjusting the setpoint with
the keys UP and DOWN.
Please note that the setpoint can only be changed within the set setpoint limits.
The time can be adjusted with the SET time key in the same way.
General reference
Note that the value is transferred to the captive memory and is safe also after power failure.
Para-
meter
Function Adjustment
range
Standard
setting
Customer
setting
S1
Cold room setpoint S1
Please note: during night time
reduction the setpoint S1 is
decreased by the value of H6
to a new setpoint S1’
S1’ = S1 + H6
r1...r2 0.0°C
T1
Actual time
00:00 ... 23:59