Value
"Light"
"Blue key"
Control LED
"blue key"
"Red key"
0
independent
independent
see left column
independent
1
off with „cooling off“
independent
see left column
independent
2
independent
off with „cooling off“
see left column
independent
3
off with „cooling off“
off with „cooling off“
see left column
independent
4
independent
independent
see left column
off with „cooling off“
5
off with „cooling off“
independent
see left column
off with „cooling off“
6
independent
off with „cooling off“
see left column
off with „cooling off“
7
off with „cooling off“
off with „cooling off“
see left column
off with „cooling off“
8
independent
Adjusting Y1
like U parameter: 7*
independent
9
off with „cooling off“
Adjusting Y1
like U parameter: 7*
independent
10
independent
Adjusting Y1
like U parameter: 7*
independent
11
off with „cooling off“
Adjusting Y1
like U parameter: 7*
independent
12
independent
Adjusting Y1
like U parameter: 7*
off with „cooling off“
13
off with „cooling off“
Adjusting Y1
like U parameter: 7
*
off with „cooling off“
14
independent
Adjusting Y1
like U parameter: 7*
off with „cooling off“
15
off with „cooling off“
Adjusting Y1
like U parameter: 7*
off with „cooling off“
16
independent
independent
see left column
independent
17
off with „cooling off“
independent
see left column
independent
18
independent
off with „cooling off“
see left column
independent
19
off with „cooling off“
off with „cooling off“
see left column
independent
20
independent
independent
see left column
off with „cooling off“
21
off with „cooling off“
independent
see left column
off with „cooling off“
22
independent
off with „cooling off“
see left column
off with „cooling off“
23
off with „cooling off“
off with „cooling off“
see left column
off with „cooling off“
24
independent
Adjusting Y1
like U parameter: 8*
independent
25
off with „cooling off“
Adjusting Y1
like U parameter: 8*
independent
26
independent
Adjusting Y1
like U parameter: 8*
independent
27
off with „cooling off“
Adjusting Y1
like U parameter: 8*
independent
28
independent
Adjusting Y1
like U parameter: 8*
off with „cooling off“
29
off with „cooling off“
Adjusting Y1
like U parameter: 8*
off with „cooling off“
30
independent
Adjusting Y1
like U parameter: 8*
off with „cooling off“
31
off with „cooling off“
Adjusting Y1
like U parameter: 8*
off with „cooling off“
(*) The control LED of the blue key is either parametered to the switching function “current input”
(regulates always) or “current input + cooling on” (regulates only if cooling is on and no defrosting
takes place).
U1-U6: Function of the outputs K1-K6
Each output controlled by the software can be optionally assigned to each of the available relays.
Thus a variety of applications can be realised with the available relays.
The setting “6” (ventilator) is only used with units without number of revolutions control. The
correspondingly configured relay is switched on if the ventilator speed is > 0%.
YA: Activation of characteristic curve
There are two operating modes to choose from: 0...20mA and 4...20mA
(accepted value range
for setting “1”: 0...21,5mA
for setting “2“: 3,5...21,5mA)
Y0: Indication of the measuring value of current input
The actual value is indicated according to parameters Y4 and Y5.
Y1: Setpoint