- Adjustable response of the fl ow temperature to sensed room temperature
- Calibration of the room sensor
- Delay to fl ow temperature compensation due to external temperature up to a maximum of
3 hours
- Holiday
Programme
- Frost protection system based on external temperature or room temperature
- Remote activation via telephone if no external room sensor fi tted (external relay required)
- Optimisation of compensation slope based on room temperature and external temperature
with optimum start time adjustment
- Hot water Anti-legionella bacteria function (65°C)
- Option of switching off internal room sensor
- 2-wired communication (scom-bus)
- Display in 6 different languages
- External display of KM628 functions with display of status, operating hours, number of starts,
degree of modulation and temperatures.
E6.1111
This is a control system for the weather dependent control of two secondary heating circuits. In
addition, a hot water circuit can also be controlled at two different Set Points. All the settings can
be made separately for each secondary circuit. This E6 controller can be further extended with an
optimisation controller system for each secondary group (BM). The weather dependent control of
the boiler is done indirectly by the E6.1111.
There are the following additional features to the BME:
- The maximum fl ow temperature can be set for each heating circuit
- The compensation slope can be manipulated with a parallel displacement to the desired fl ow
temperature of the boiler
- Time controlled hot water re-circulation pump
- Pump-kick
function
- DCF receiver for internal clock (optional receiver required)
- Communication over a CAN-bus
- Integrated relay and sensor test
- Can be used in stand-alone operation
KKM
This is a boiler cascade manager with which up to 8 boilers can be connected in cascade and an
extra on/off boiler can be operated. The KKM also has the same functional features as the E6.1111.
Connecting terminals
Terminal: Description:
L1-N-Earth
Supply for the boiler should be installed with 6A fuse protection. If miniature
circuit breakers are used, these should have C Rated characteristics.
1-3
Lockout circuit (230 Vac from boiler, 1A). If the connection between the two ter-
minals is broken, the boiler will immediately go into a lockout condition and will
remain out of operation until this connection is restored and has been reset using
the lockout reset button.
4-5
On/Off. By connecting the two terminals to each other, the boiler is switched
from the standby mode to the operating mode and can start when there is a heat
requirement. These terminals can be used for thermostatic functions for the
boiler. If the circuit is interrupted, the boiler goes into the stand-by mode, except
for hot water preparation.
6-7
A hot water temperature sensor can be connected to these terminals. These are
recognised automatically by the boiler controller when the supply voltage is
switched on. The reading from this sensor is used for controlling the hot water
temperature.
8-9
External fl ow temperature adjustment. A 0-5 Vdc (-10 to+90°C) analogue signal
can be applied at these terminals. If the voltage is less than 1 Vdc, it will change
over to the internal set fl ow temperature (set at P1).