Notes on Safety
Commissioning Instructions I/O Terminal Module
7
ID 441758.05
WE KEEP THINGS MOVING
2
2.4
Installation and connection
Installation and connection work are only permitted after the device has been isolated from the power!
The accessory installation instructions allow the following actions during the installation of accessories:
•
The housing in the upper slot can be opened
•
The housing in the bottom slot can be opened.
Opening the housing in another place or for other purposes is not permitted.
The accessory installation instructions allow the following actions during the installation of accessories:
•
The housing in the upper slot can be opened.
Opening the housing in another place or for other purposes is not permitted.
Use only copper lines. For the line cross sections to be used, refer to DIN VDE 0298-4 or DIN EN 60204-1
Appendix D and Appendix G.
Protect the device from falling parts (pieces of wire, leads, metal parts, and so on) during installation or other
tasks in the switching cabinet. Parts with conductive properties inside the inverter can cause short circuits or
device failure.
The motor must have an integrated temperature monitor with basic isolation in acc. with EN 61800-5-1 or
external motor overload protection must be used.
The permissible protection class is protective ground. Operation is not permitted unless the protective
conductor is connected in accordance with the regulations.
Comply with the applicable instructions for installation and commissioning of motor and brakes.