![Stirling PA19W Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/stirling/pa19w/pa19w_service-manual_1380580008.webp)
8
AFTER SALES SUPPORT
1300 886 649
AUS
MODEL: PA19W PRODUCT CODE: 703227 11/2020
9.4 Ensure that the outlet for the vacuum pump is not close to any ignition sources
and that ventilation is available.
10 Charging procedures
In addition to conventional charging procedures, the following requirements shall be
followed.
10.1 Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimise
the amount of refrigerant contained in them.
– Cylinders shall be kept upright.
– Ensure that the refrigeration system is earthed prior to charging the system
with refrigerant.
– Label the system when charging is complete (if not already).
– Extreme care shall be taken not to overfill the refrigeration system.
10.2 Prior to recharging the system, it shall be pressure-tested with the appropriate
purging gas.
10.3 The system shall be leak-tested on completion of charging but prior to
commissioning. A follow up leak test shall be carried out prior to leaving the
site.
11. Decommissioning
Before carrying out this procedure, it is essential that the technician is completely
familiar with the equipment and all its detail. It is recommended good practice
that all refrigerants are recovered safely. Prior to the task being carried out, an oil
and refrigerant sample shall be taken in case analysis is required prior to re-use of
reclaimed refrigerant. It is essential that electrical power is available before the task
is commenced.
11.1 Become familiar with the equipment and its operation.
11.2 Isolate system electrically.
11.3 Before attempting the procedure, ensure that:
–
mechanical handling equipment is available, if required, for handling
refrigerant cylinders
–
all personal protective equipment is available and being used correctly
–
the recovery process is supervised at all times by a competent person
–
recovery equipment and cylinders conform to the appropriate standards.
11.4 Pump down refrigerant system, if possible.
11.5 If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
11.6 Ensure that the cylinder is situated on the scales before recovery takes place.
Service Instructions (Cont.)