AFTER SALES SUPPORT

1300 886 649

[email protected]

AUS

MODEL: PA19W   PRODUCT CODE: 703227    11/2020

4.   Repairs to sealed components

4.1   During repairs to sealed components, all electrical supplies shall be 

disconnected from the equipment being worked upon prior to any removal 
of sealed covers, etc. If it is absolutely necessary to have an electrical 
supply to equipment during servicing, then a permanently operating form 
of leak detection shall be located at the most critical point to warn of a 
potentially hazardous situation.

4.2   Particular attention shall be paid to the following to ensure that by 

working on electrical components, the casing is not altered in such a 
way that the level of protection is affected. This shall include damage to 
cables, excessive number of connections, terminals not made to original 
specification, damage to seals, incorrect fitting of glands, etc. Ensure that 
the apparatus is mounted securely.

4.3   Ensure that seals or sealing materials have not degraded to the point that 

they no longer serve the purpose of preventing the ingress of flammable 
atmospheres. Replacement parts shall be in accordance with the 
manufacturer’s specifications.

 

 NOTE

 The use of silicon sealant can inhibit the effectiveness of some types 

of leak detection equipment.

 

 Intrinsically safe components do not have to be isolated prior to working on 
them.

5.  Repair to intrinsically safe components

5.1   Do not apply any permanent inductive or capacitance loads to the circuit 

without ensuring that this will not exceed the permissible voltage and 
current permitted for the equipment in use.

5.2   Intrinsically safe components are the only types that can be worked on 

while live in the presence of a flammable atmosphere. The test apparatus 
shall be at the correct rating.

5.3   Replace components only with parts specified by the manufacturer. Other 

parts may result in the ignition of refrigerant in the atmosphere from a leak.

6. Cabling

 

 Check that cabling will not be subject to wear, corrosion, excessive 
pressure, vibration, sharp edges or any other adverse environmental 
effects. The check shall also take into account the effects of aging or 
continual vibration from sources such as compressors or fans.

7.  Detection of flammable refrigerants

 

 Under no circumstances shall potential sources of ignition be used in the 
searching for or detection of refrigerant leaks. A halide torch (or any other 
detector using a naked flame) shall not be used.

Service Instructions (Cont.)

Содержание PA19W

Страница 1: ...AFTER SALES SUPPORT 1300 886 649 info tempo org AUS MODEL PA19W PRODUCT CODE 703227 11 2020 Model Number PA19W Wi Fi Portable Air Conditioner 1 9kW Cooling SERVICE MANUAL ...

Страница 2: ...as open flames an operating ignition gas appliance or an operating electric heater Do not expose the appliance to high heat sparks and open flames Do not pierce or burn the appliance Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer Be aware that refrigerants may not contain an odour The ratings of the fuse installed in the built in ...

Страница 3: ...stallation of pipe work shall be kept to a minimum Pipe work shall be protected from physical damage and shall not be installed in an unventilated space Compliance with national gas regulations shall be observed Mechanical connections made by brazing or welding shall be accessible for maintenance purposes Table Minimum room area m2 R290 LFL kg m3 h0 m Charge amount M kg Minimum room area m2 0 152k...

Страница 4: ...riate refrigerant detector prior to and during work to ensure the technician is aware of potentially toxic or flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsically safe 1 4 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any...

Страница 5: ... being used the secondary circuit shall be checked for the presence of refrigerant marking to the equipment continues to be visible and legible Markings and signs that are illegible shall be corrected refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are const...

Страница 6: ...th the manufacturer s specifications NOTE The use of silicon sealant can inhibit the effectiveness of some types of leak detection equipment Intrinsically safe components do not have to be isolated prior to working on them 5 Repair to intrinsically safe components 5 1 Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible...

Страница 7: ... by means of shut off valves in a part of the system remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing process 9 Removal and evacuation 9 1 When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However for flammable refrigerants it is important that best practi...

Страница 8: ...ried out prior to leaving the site 11 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed ...

Страница 9: ... are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Empty recovery cylinders a...

Страница 10: ... specially equipped for servicing units with flammable refrigerants Ensure sufficient ventilation at the repair place Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrigerant leak is possible Discharge capacitors in a way that won t cause any spark The standard procedure to short circuit the capacitor terminals usually creates sparks Reassemble sealed enclosur...

Страница 11: ... spark Remove the refrigerant If the recovery is not required by national regulations drain the refrigerant to the outside Take care that the drained refrigerant will not cause any danger In doubt one person should guard the outlet Take special care that drained refrigerant will not float back into the building Evacuate the refrigerant circuit Purge the refrigerant circuit with nitrogen for 5 min ...

Страница 12: ...ecommend that you ask your licensed service technician to fill in the details below so you have them on record should you need to contact the technician in the future Please fill in the details below Name of service technician Licence number Date of service Signature Service Manual Version 1 1 July 2020 Technical specifications Model PA19W Cooling capacity 1 9kW Refrigerant quantity R290 140g Perm...

Отзывы: