13.5 If compressors or compressor oils are to be removed, ensure that they
have been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant. The evacuation process shall
be carried out prior to returning the compressor to the suppliers. Only electric
heating to the compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.
14. Information about the correct working procedures:
Every working procedure that affects safety means shall only be carried out by
competent persons according to the below points:
14.1
Commissioning
• Ensure that the floor area is sufficient for the refrigerant charge or that the
ventilation duct is assembled in a correct manner.
• Connect the pipes and carry out a leak test before charging with refrigerant.
• Check safety equipment before putting into service.
14.2
Maintenance
• Portable equipment shall be repaired outside or in a workshop specially
equipped for servicing units with flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by refrigerant
loss and a refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark. The standard
procedure to short-circuit the capacitor terminals usually creates sparks.
• Reassemble sealed enclosures accurately. If seals are worn, replace them.
• Check safety equipment before putting into service.
14.3
Repair
• Portable equipment shall be repaired outside or in a workshop specially
equipped for servicing units with flammable refrigerants.
• Ensure sufficient ventilation at the repair place.
• Be aware that malfunction of the equipment may be caused by refrigerant
loss and a refrigerant leak is possible.
• Discharge capacitors in a way that won’t cause any spark.
• When brazing is required, the following procedures shall be carried out in the
right order:
– Remove the refrigerant. If the recovery is not required by national
regulations, drain the refrigerant to the outside. Take care that the drained
refrigerant will not cause any danger. In doubt, one person should guard
the outlet. Take special care that drained refrigerant will not float back into
the building.