Stirling PA19W Скачать руководство пользователя страница 7

7

AFTER SALES SUPPORT

1300 886 649

[email protected]

AUS

MODEL: PA19W   PRODUCT CODE: 703227    11/2020

8.  Leak detection methods

 

 The following leak detection methods are deemed acceptable for all refrigerant 
systems.

8.1   Electronic leak detectors may be used to detect refrigerant leaks but, in the 

case of flammable refrigerants, the sensitivity may not be adequate, or may 
need re-calibration. (Detection equipment shall be calibrated in a refrigerant-
free area.) Ensure that the detector is not a potential source of ignition and is 
suitable for the refrigerant used. Leak detection equipment shall be set at a 
percentage of the LFL (lower flammable limit, 0.038 kg/m

3

) of the refrigerant 

and shall be calibrated to the refrigerant employed, and the appropriate 
percentage of gas (25% maximum) is confirmed.

8.2   Leak detection fluids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with 
the refrigerant and corrode the copper pipe work.

8.3   If a leak is suspected, all naked flames shall be removed/extinguished.

8.4   If a leakage of refrigerant is found which requires brazing, all of the refrigerant 

shall be recovered from the system, or isolated (by means of shut off valves) 
in a part of the system remote from the leak. Oxygen-free nitrogen (OFN) 
shall then be purged through the system both before and during the brazing 
process.

9.  Removal and evacuation

9.1   When breaking into the refrigerant circuit to make repairs – or for any other 

purpose – conventional procedures shall be used. However, for flammable 
refrigerants it is important that best practice is followed since flammability is a 
consideration. The following procedure shall be adhered to:

– remove refrigerant
– purge the circuit with inert gas
– evacuate
– purge again with inert gas
– open the circuit by cutting or brazing.

9.2   The refrigerant charge shall be recovered into the correct recovery cylinders. 

The system shall be “flushed” with OFN to render the unit safe. This process 
may need to be repeated several times. Compressed air or oxygen shall not be 
used for purging refrigerant systems.

9.3   Flushing shall be achieved by breaking the vacuum in the system with OFN 

and continuing to fill until the working pressure is achieved, then venting to 
atmosphere, and finally pulling down to a vacuum. This process shall be 
repeated until no refrigerant is within the system. When the final OFN charge is 
used, the system shall be vented down to atmospheric pressure to enable work 
to take place. This operation is absolutely vital if brazing operations on the pipe 
work are to take place.

Service Instructions (Cont.)

Содержание PA19W

Страница 1: ...AFTER SALES SUPPORT 1300 886 649 info tempo org AUS MODEL PA19W PRODUCT CODE 703227 11 2020 Model Number PA19W Wi Fi Portable Air Conditioner 1 9kW Cooling SERVICE MANUAL ...

Страница 2: ...as open flames an operating ignition gas appliance or an operating electric heater Do not expose the appliance to high heat sparks and open flames Do not pierce or burn the appliance Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer Be aware that refrigerants may not contain an odour The ratings of the fuse installed in the built in ...

Страница 3: ...stallation of pipe work shall be kept to a minimum Pipe work shall be protected from physical damage and shall not be installed in an unventilated space Compliance with national gas regulations shall be observed Mechanical connections made by brazing or welding shall be accessible for maintenance purposes Table Minimum room area m2 R290 LFL kg m3 h0 m Charge amount M kg Minimum room area m2 0 152k...

Страница 4: ...riate refrigerant detector prior to and during work to ensure the technician is aware of potentially toxic or flammable atmospheres Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsically safe 1 4 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any...

Страница 5: ... being used the secondary circuit shall be checked for the presence of refrigerant marking to the equipment continues to be visible and legible Markings and signs that are illegible shall be corrected refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are const...

Страница 6: ...th the manufacturer s specifications NOTE The use of silicon sealant can inhibit the effectiveness of some types of leak detection equipment Intrinsically safe components do not have to be isolated prior to working on them 5 Repair to intrinsically safe components 5 1 Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible...

Страница 7: ... by means of shut off valves in a part of the system remote from the leak Oxygen free nitrogen OFN shall then be purged through the system both before and during the brazing process 9 Removal and evacuation 9 1 When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used However for flammable refrigerants it is important that best practi...

Страница 8: ...ried out prior to leaving the site 11 Decommissioning Before carrying out this procedure it is essential that the technician is completely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed ...

Страница 9: ... are employed Ensure that the correct number of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated shut off valves in good working order Empty recovery cylinders a...

Страница 10: ... specially equipped for servicing units with flammable refrigerants Ensure sufficient ventilation at the repair place Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrigerant leak is possible Discharge capacitors in a way that won t cause any spark The standard procedure to short circuit the capacitor terminals usually creates sparks Reassemble sealed enclosur...

Страница 11: ... spark Remove the refrigerant If the recovery is not required by national regulations drain the refrigerant to the outside Take care that the drained refrigerant will not cause any danger In doubt one person should guard the outlet Take special care that drained refrigerant will not float back into the building Evacuate the refrigerant circuit Purge the refrigerant circuit with nitrogen for 5 min ...

Страница 12: ...ecommend that you ask your licensed service technician to fill in the details below so you have them on record should you need to contact the technician in the future Please fill in the details below Name of service technician Licence number Date of service Signature Service Manual Version 1 1 July 2020 Technical specifications Model PA19W Cooling capacity 1 9kW Refrigerant quantity R290 140g Perm...

Отзывы: