73
16.2 Inputs
In this submenu, the type of the sensor connected
can be adjusted for each individual input. the fol-
lowing types can be selected:
• switch
• KtY
• pt500
• rta11-m
• pt1000
• none
ATTENTION!
System damage!
selecting the wrong sensor type
will lead to unwanted controller
actions. In the worst case, system
damage can occur!
Î
Make sure that the right sen-
sor type is selected!
If KtY, pt500 or pt1000 are selected, the channel
offset appears, in which an individual offset can be
adjusted for each sensor.
Î
In order to select a sensor for the offset adjust-
ment, select the corresponding menu item by
pressing button
5
Î
to adjust the sensor offset, select the desired
value by pressing buttons
or
4
, then con-
firm by pressing button
5
In- / Outputs / Inputs
CS sensor offset
If a Cs10 irradiation sensor is to be connected, an
offset has to be carried out before the connection is
made.
to carry out the offset, proceed as follows:
Î
adjust the Cs type in the type channel
Î
select the offset channel
Î
Confirm the reset enquiry with Yes
Î
select back to return to the Inputs menu, then
connect the Cs sensor
Note:
When Grundfos Direct sensors
tm
are used, the
sensor ground common terminal block must
be connected to pe (see chap. 2.2).
adjustment
channel
Description
adjustment range / selection Factory setting
s1 ... s12
sensor input selection
-
-
type
selecting the sensor type
switch, KtY, pt500, rta11-m,
pt1000, none
pt1000
offset
sensor offset
-15.0 ... +15.0 K
0.0 K
Imp. 1 ... 3
Impulse input selection
-
-
type
selecting the sensor type
Impulse, switch, KtY, pt500,
rta11-m, pt1000, none
Impulse
Vol./Imp.
Impulse rate
0.1 ... 100.0
1.0
Cs10
Cs10 input
-
-
type
Cs type
a ... K
e
offset
Delete offset
Yes, no
no
Ga1, 2
analog Grundfos Direct sensortm
-
-
type
Grundfos Direct sensor
tm
type
rps, VFs, none
none
min.
minimum pressure (if type = rps)
0.0 ... 0.5 bar
0.0 bar
max.
maximum pressure (if type = rps)
0.1 ... 16.0 bar
0.6 bar
min.
minimum flow rate (if type = VFs)
1 ... 39 l/min
2 l/min
max.
maximum flow rate (if type = VFs)
2 ... 400 l/min
40 l/min
Gd1, 2
Digital Grundfos Direct sensortm
-
-
type
Grundfos Direct sensor
tm
type
rpD, VFD, none
none
if type = VFD:
measuring range selection
10 - 200 l/min, 5 - 100 l/min,
2 - 40 l/min, 2 - 40 l/min (fast),
1 - 20 l/min, 1 - 12 l/min*
1 - 12 l/min
* For the Inputs Gd1 and Gd2, the following sensor combinations are possible:
- 1 x rpD, 1 x VFD
- 2 x VFD, but with different measuring ranges only
295931-36390-8667 SOM 8 plus_en.indb 73
20.10.2011 13:14:58