67
adjustment channel Description
adjustment range / selection Factory setting
Demand
Demand relay selection
system dependent
system dependent
loading pump
loading pump option
Yes, no
no
relay
loading pump relay selection
system dependent
system dependent
overrun time
overrun option
Yes, no
no
Duration
overrun time
1 ... 10 min
1 min
mode
operating mode
Boiler, therm.
therm.
sensor 1
sensor 1
system dependent
system dependent
sensor 2
sensor 2 (only if mode = Boiler) system dependent
system dependent
ton
switch-on temperature
0 ... 94 °C [32 ... 202 °F]
40 °C [104 °F]
toff
switch-off temperature
1 ... 95 °C [34 ... 204 °F]
45 °C [114 °F]
timer
timer option
Yes, no
no
timer
timer
-
-
Days of the week
Day selection
all days, monday ... sunday,
Continue
-
timer
time frame adjustment
00:00 ... 23:45
-
Funct.
activation / Deactivation
activ., Deactivated
Deactivated
Heating / Opt. functions / Add new function... / DHW heating
11 HQM
In the
HQM
menu, up to seven internal heat quan-
tity measurements can be activated and adjusted.
By selecting the menu item
New HQM
, a new heat
quantity measurement can be activated.
a menu opens in which all adjustments required for
the heat quantity measurement can be made.
If the
Flow rate sensor
option is activated, the im-
pulse input or, if available, a Grundfos Direct sensor™
can be selected. Grundfos Direct sensors™ are only
available if they have been previously registered in
the In-/outputs menu. the impulse rate must be ad-
justed in that menu as well.
If the
Flow rate sensor
option is deactivated, the
controller calculates the heat quantity by means
of a fixed flow rate value. this is called heat quan-
tity balancing. For this purpose, the flow rate must
be read from the flowmeter at 100 % pump speed
and adjusted in the adjustment channel
Flow rate
.
In addition to that, a
Relay
must be allocated. Heat
quantity balancing is in effect whenever the alloca-
ted relay is active.