37
the Cs bypass function is a different possibility to
activate the collector circuit. to enable the use of the
Cs bypass function, a Cs10 irradiation sensor has to
be connected.
When the Cs bypass function is activated, the irra-
diation value is the switch-on condition for the col-
lector circuit.
the relay remains switched on if the irradiation val-
ue is exceeded for the delay time. When solar load-
ing begins or the irradiation value remains below
the switch-on value for the delay time, the relay is
switched off.
When the
Stmax off
option is activated, collector
circuit activation is suppressed as long as all store
temperatures are above their respective maximum
temperatures.
CS bypass
Solar / Opt. functions / Add new function... / CS bypass
adjustment channel
Description
adjustment range / selection Factory setting
Collector
Collector field
system dependent
system dependent
Irrad.
switch-on irradiation
100 ... 500 W / m²
200 W / m²
Delay
Delay time
10 ... 300 s
120 s
stmax off
stmax switch-on suppression
Yes, no
Yes
Funct.
activation / Deactivation
activ., Deactivated
Deactivated
295931-36390-8667 SOM 8 plus_en.indb 37
20.10.2011 13:14:38