INSTRUCTION MANUAL
UP-2/L
_____________________________________________________________________________________
STI S.r.l.
– Via Dei Caravaggi 15, 24040 Levate (BG) – ITALY www.imi-critical.com
Manual 4019
– rev.06 07/2019 – UP-2/L
– 8 –
Technical features
Standard materials
Positioner’s body
Aluminum die-cast
Internal levers
Aluminum die-cast
Top manifold
Aluminum die-cast / Aluminum
Cam
Hostaform
TM
Spool valve
Brass/Stainless steel
Diaphragm
Epichlorohydrin
Connections
Connections for model UP-2/L (with or without change-over plate)
Supply
1/4” NPTF
Signal
1/4
” NPTF
Outputs
1/4
” NPTF
Pressure gauges
1/8
” NPTF
Connections for model UP-2/L2
Supply
1/2
” NPTF
Signal
1/4
” NPTF
Outputs
1/2
” NPTF
Pressure gauges
1/8
” NPTF
Supply
Max. 665 kPa (100 psig / 7 bar)
Operating temperature
- 20°C / + 70°C (- 4°F / + 158°F)
(- 40°C / + 70°C and - 20°C / + 85°C available on request)
Storage temperature
- 40°C / + 70°C (- 40°F / + 194°F)
Standard cam
(linear, 4 shapes, direct
or reverse action)
21 ÷ 105 kPa (3 ÷ 15 psi / 4 ÷ 20 mA)
– working angle 0 ÷ 45°
21 ÷ 105 kPa (3 ÷ 15 psi / 4 ÷ 20 mA)
– working angle 0 ÷ 65°
21 ÷ 63 kPa (3 ÷ 9 psi / 4 ÷ 12 mA)
– working angle 0 ÷ 45°
63 ÷ 105 kPa (9 ÷ 15 psi / 12 ÷ 20 mA)
– working angle 0 ÷ 45°
21 ÷ 63 kPa (3 ÷ 9 psi / 4 ÷ 12 mA)
– working angle 0 ÷ 65°
63 ÷ 105 kPa (9 ÷ 15 psi / 12 ÷ 20 mA)
– working angle 0 ÷ 65°
Zero suppression
0 ÷ 63 kPa (0 ÷ 9 psi)
Range adjustment
30% of the range
Air consumption
0,6 SCFM (1,04 Nm³/h) in balanced condition for standard model
with ¼” NPT F connections.
0,8 SCFM (1.3 Nm³/h) in balanced condition for special model
with ½” NPT F connections.
(with air supply at 420 kPa
– 60 psi)
Sensitivity
0,25% better than the considered signal range
Capacity (max. load)
15 SCFM (25
Nm³/h) with ¼” NPT F connections.
36 SCFM (60
Nm³/h) with ½” NPT F connections.
(with air supply at 590 kPa
– 85 psi)
Accuracy
With linear cam ± 1%
Accessories
Electro-pneumatic version
– Pressure gauges – Change-over plate with
by-pass valve
– Stainless steel spool valve – Special construction for
corrosive environment (electronic or pneumatic)
– Integrated air-lock
Amplification
A signal or stroke deviation smaller than 2% generates the maximum
output pressure.
Weights
¼” 3,9 kg – ½” 4 kg (complete of support)