Manual activation in case of fire/smoke/alarm

Daily ventilation

Automatic ventilation control

Closing with wind/rain detector

Smoke heat extraction / opening windows

Smoke heat extraction / closing windows

Smoke heat extraction / closing windows

Opening windows

Closing windows

Note

Press the red OPEN switch      at a SHE manual call point

the

windows open completely

the red LED display        - SHE

activated - is shining at all SHE manual call points

the

continuous acoustical signal rings out

the ventilation function is

out of order.

Press the switch “closed”

at a SHE manual call point

the

windows are closing

the red LED display      - SHE activated -

goes out at all SHE manual call points

the continuous

acoustical signal goes out

the ventilation function is working

again.

the continuous acoustical signal

rings out

Set the automatic detectors free from smoke by blowing out or
replace them in case of heavy soiling.
Press the RESET switch on the basic circuit control board

the

windows are closing

the red display in the automatic detectors

goes out

the red LED display      - SHE activated - goes out at

all SHE manual call points

the continuous acoustical signal

goes out

the ventilation function is working again.

The windows can also be closed using the Closed switch        at a
SHE manual call point. In this case the smoke detector line is not
reset.

Press the switch “open” at the vent switch

the windows open

completely. (Interruption of the opening by pressing both switches
together (Open and Closed) = STOP

the “Ventilation Open”

display in the control centre lights up.

Press the switch “closed” at the vent switch

the windows close

completlely. (Interruption of the opening by pressing both switches
together (Open and Closed) = STOP

the “ventilation open”

display in the control centre goes out

in case of mains or

battery failure, the windows close immediately.

If activated (see  putting into operation)

the windows are closing

automatically after 10 min.

in case of mains or battery failure,

the windows close immediately.

If a wind/rain detector or a rain sensor is connected, the windows
close automatically in case of beginning winds and/or rainfall
“Ventilation Open” display flashes

vent switch out of order

the windows close immediately in case of power or battery failure.

: The ventilation function is out of order  or locked in

case of power or battery failure or SHE activation in order to save
battery power. All acoustical signals (SHE activation and
malfunction message) only ring out when the door is closed or the
door contact switch is pressed.

Automatic activation in case of fire/smoke/alarm

if automatic detectors are connected only

Smoke reaches the automatic detectors

the windows are

opened completely

the red display in the automatic detector is

shining

the red LED display       - SHE activated - is shining at

all SHE manual call points

the ventilation function is out of order.

Smoke heat extraction / opening windows

Funktionsbeschreibung

Description of operating

Manuelle Auslösung bei Feuer/Brand/Alarm

Tägliches Lüften

Schließen mit 10 Min. Automatik

Schließen mit Wind-/Regenmelder

Rauchabzug / Fenster öffnen

Rauchabzug / Fenster schließen

Fenster öffnen

Fenster schließen

Hinweis

rote AUF-Taste      in einer RWA-Bedienstelle drücken

Fenster

werden vollständig geöffnet

rote LED-Anzeige       - RWA

ausgelöst - leuchtet in allen RWA-Bedienstellen

akustisches

Dauersignal ertönt

die Lüftungsfunktion ist außer Betrieb.

ZU-Taste        in einer RWA-Bedienstelle drücken

Fenster

schließen

die rote LED-Anzeige       - RWA ausgelöst - erlöscht

in allen RWA-Bedienstellen

akustisches Dauersignal verstummt

Lüftungsfunktion ist wieder in Betrieb.

akustisches Dauersignal ertönt

Automatische Melder von Rauch befreien (durch Ausblasen bzw.
bei starker Verschmutzung ersetzen).
Taste RWA-RESET in der Steuerzentrale drücken

Fenster

schließen

rote Anzeige im automatischen Melder erlischt

die

rote LED-Anzeige      - RWA ausgelöst - erlischt in allen RWA-
Bedienstellen

akustisches Dauersignal verstummt

die

Lüftungsfunktion ist wieder in Betrieb.

Über die ZU-Taste        in einer RWA-Bedienstelle können die
Fenster ebenfalls geschlossen werden. Hierbei wird die
Rauchmelderlinie nicht zurückgesetzt.

am internen oder externen Lüftungstaster AUF-Taste kurz drücken

Fenster wird vollständig geöffnet. (Unterbrechen des

Öffnungsvorgangs durch kurzes gemeinsames Antippen beider
Tasten (Auf und Zu) = STOP

die Anzeige “Lüftung Auf” in der

Steuerzentrale leuchtet.

am Lüftungstaster ZU-Taste kurz drücken

Fenster schließen

vollständig. (Unterbrechen des Schließvorgangs durch kurzes
gemeinsames Antippen beider Tasten (Auf und Zu) = STOP

die

Anzeige “Lüftung Auf” in der Steuerzentrale erlischt

bei Netz-

oder Akkuausfall schließen die Fenster sofort.

ist die 10 Min. Automatik aktiv (siehe Inbetriebnahme)

schließen

die Fenster selbständig nach 10 Min.

bei Netz- oder Akkuausfall

schließen die Fenster sofort.

Ist ein Wind-/Regenmelder oder Regensensor angeschlossen,
schließen die Fenster bei einsetzendem Wind und/oder Regen
selbständig

die Anzeige “Lüftung Auf” in der Steuerzentrale

blinkt

die Lüftungsfunktion ist außer Betrieb

bei Netz- oder

Akkuausfall schließen die Fenster sofort.

: Bei Ausfall der Netz- oder Akkuspannung oder

bei RWA-Auslösung ist die Lüftungsfunktion aus Gründen der
Akkuschonung außer Betrieb bzw. gesperrt. Alle akustischen
Signale ertönen nur bei geschlossener Tür oder gedrücktem
Türkontaktschalter.

Automatische Auslösung bei Feuer/Brand/Alarm

nur wenn automatische Melder angeschlossen sind.

Rauch erreicht die automatischen Melder

Fenster werden

vollständig geöffnet

rote Anzeige im automatischen Melder

leuchtet

rote LED-Anzeige       - RWA ausgelöst - leuchtet in

allen RWA-Bedienstellen

die

Lüftungsfunktion ist außer Betrieb.

Rauchabzug / Fenster öffnen

Rauchabzug / Fenster schließen

4

Содержание RZ VdS 2A

Страница 1: ...rm prozessorgesteuert vielfältige Anschlussmöglichkeiten VdS zertifiziert Funktion Tägliches Lüften 230 V AC 50 Hz Höhe x Breite x Tiefe with integrated SHE manual call point and vent switch function daily ventilation 1 SHE group and 24 V power supply emergency power batteries and charging unit parallel operation line monitoring of alarm circuits autom detectors and SHE man call points line monito...

Страница 2: ...he automatic opening and closing of the stated types of windows For further application please contact the manufacturer Required mounting material is to be adapted to the frame and the corresponding load and is to be completed if necessary Any supplied mounting material is only part of the required amount If the equipment is employed in smoke heat extraction systems in short SHE they must be check...

Страница 3: ...r Wasser und Schmutz Routing of cables and electrical connections only to be done by a qualified electrician Power supply leads 230 V AC to be fused separately by the customer Keep power supply leads sheathed until the mains terminal DIN and VDE regulations to be observed for the installation VDE 0100 Setting up of high voltage installations up to 1000 V VDE 0815 Installation cables and wires VDE ...

Страница 4: ...splay SHE activated is shining at all SHE manual call points the ventilation function is out of order Smoke heat extraction opening windows Funktionsbeschreibung Description of operating Manuelle Auslösung bei Feuer Brand Alarm Tägliches Lüften Schließen mit 10 Min Automatik Schließen mit Wind Regenmelder Rauchabzug Fenster öffnen Rauchabzug Fenster schließen Fenster öffnen Fenster schließen Hinwe...

Страница 5: ...t 24 V max 0 5 A 5 Funktionsbeschreibung Description of operating OK OK LED Anzeigen In der Steuerzentrale in den RWA Bedienstellen Netz oder Akkuausfall Störung der Leitungsüberwachung zu den Antrieben RWA Bedienstellen oder automatischen Meldern eine Störung steht an Leitungsanschluss defekt Netz und oder Akku defekt gleichzeitig ertönt eine akustische Störmeldung Die rote LED Anzeige RWA ausgel...

Страница 6: ...n NYM O 2 x 1 5 mm or 3 x 1 5 mm dep on the monitoring mode see wiring diagram Netz 230 V 50Hz NYM I 3 x 1 5 mm Separat abschaltbaren Stromkreis vorsehen Vor unbeabsichtigtem Abschalten sichern Mains 230 V 50Hz NYM O 3 x 1 5 mm provide a separately disconnetible circuit Secure against unintentinal switching off autom Melder autom detector Abstand max 1 2 m distance max 1 2 m Wind Regenmelder WRM 2...

Страница 7: ...ul im letzten oder einzigen autom Melder oder falls keine Melder angeschlossen werden aktives Endmodul in der Steuerzentrale einklemmen Install active end module in the last or only autom detector or if no detectors are to be connected install active end module in the control centre 24V 5V 5V 24V 24V 24V 5V 5V 24V Bei Anschluss von mehreren Antrieben Anschlussplan auf Seite 8 beachten Achtung Atte...

Страница 8: ...e des Tasters jumper setting for the TRZ at the rear of the switch GEM 4 together 4 AUF 3 Open 3 ZU 2 closed 2 LED 1 ein Lüftungstaster Auf Zu gemeinsam Stop one vent switch open closed together Stop ein Lüftungstaster mit Sicht anzeige LTA 25 one vent switch with visual display LTA 25 ein Antrieb gesamt max 2 A Stromaufnahme one drive total power consumption max 2 A Wind Regen WRM 24V RM 24 Wind ...

Страница 9: ... 13 14 15 16 17 18 19 L1 N PE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Rauchmelder 24V Rauchmelder smoke detector smoke detector 24 V DC max 100 mA WR GND WR Signal Auslösung Auslösung Störung Störung activation activation malfunction malfunction Schließer Öffner Closer opener Lüftungstaster vent switch pot freie Kontakte potential free contacts Netz 230 V 50 Hz mains 230 V 50 H...

Страница 10: ... mechanically and electrically for fully tightened screw connections and damage the terminals plug in connectors for motors and control elements as well as if available automatic detectors and wind rain detectors 2 wire monitoring with capaciter to connect window motor or 3 wire monitoring to connect one or several window motors Start of automatic identification Absolutely necessary for initial st...

Страница 11: ...taster RWA Bedienstellen Achtung Fehlerbehebung Achtung Achtung Achtung OK OK With mains voltage with battery Visual display in the control centre door Vent switches SHE manual call points Plug on the battery connector the battery connector is polarized If it is removed make sure the polarity is correct Polarity reversal leads to destruction Max 100 secs after connecting the battery check green LE...

Страница 12: ...sche Melder Test 10 Min Automatik Test Wind Regenmelder oder Regensensor Abschließende Arbeiten OK OK OK Test emergency power supply Test automatic detectors Test 10 min automatic Test Wind Rain detector or rain sensor Completion work Disconnect power supply the green LED Operation OK goes out The yellow LED malfunction flashes An alternating acoustic signal rings out if the door is closed or the ...

Страница 13: ...s Gesetze beachten Um die RWA Anlage außer Betrieb zu nehmen muss die TRZ vom Netz getrennt werden die Batteriesicherung entfernt werden und Display operating OK is not shining The drives open without pressing a switch Vent switch with reversed function Vent switch without function Malfunction beep code chart The operating instructions of the connected components must imperatively be observed in t...

Страница 14: ...vation and malfunction Type of connection to external VdS environment category Ambient humidity Protective system Housing Housing door Housing dimensions Fuse values F1 mains fuse F2 motor fuse F3 battery fuse 230 V AC 50 Hz 10 separately fused max 0 6 A approx 150 VA 24 V DC nominal 15 25 Residal ripple 1 2 x 12 V 1 2 Ah with total discharge prot in case of low voltage monitor funct for wire brea...

Отзывы: