Sterling Power Products

Copyright 

Force unit to operate without output battery connected 
( i.e. as a power pack / live output ). 

This mode shall allow the unit to operate without needing a 
voltage on the output terminal. Hold down SETUP/ENTER 
button for 15+ seconds and let go. The boost, absorption 
and float LEDs shall flash. A green LED (18) on the right 
panel should appear and this indicates that voltage check 
is on (default mode) to change it to off (power pack) press 
the SELECT button and a red LED (24) below should turn 
on. With the red LED on the unit shall now operate without 
the need for an output voltage. Press both buttons together 
to save this setting or wait 30 seconds for the unit to reboot. 

On reboot, the 

 comes on for 

HIGH BATT TEMP LED(24)

to confirm power pack mode. 

Force to Float :

Before  accessing  float  mode  please  be  sure  you  know 
what float mode is and what voltage float mode is for your 
profile. Simply hold both buttons down for 2 seconds and 
let go. This will lock the charger into float (BLUE LED - top 
right - number 15 shall come on). The charger shall now 
remain in float and resume bulk/absorption on restarting. 
To force the unit out of float repeat the procedure.  

Force unit off / on: 

  

This  shall  deactivate  the  unit,  output  goes  to  0.0V.  Hold 

both setup and select buttons

 for 5 - 9 seconds. LEDs shall 

turn  off,  the  Bulk  LED  (blue)  shall  flash  once  every  5 
seconds. The unit will remain off, even with normal engine 
cycling  on  and  off  (although  if  the  unit’s  negative  is 
disconnected  from  the  input  battery  then  it  will  resume 
normal operation on re-connection). To turn the unit back 
on, hold the 2 buttons for 5-9 seconds. 

When OFF, the user 

can not access charger’s normal functions.

Force unit to ½ power (stays on until unit is turned off):

    

This will reduce the units power by about 50%. Hold 

setup 

button only

 for 5-9 seconds. To confirm the power reduction 

LED shall flash 5 times. This function will help reduce noise 
in the long term. To return to full power, press the setup 
button again for 5-9 seconds. 

Force unit to ½ power / low speed fan for 8 hours only 
(night mode):    

 

This will reduce the unit’s power by around 50%
for about 8 hours. 

Hold 

select button only

 for 

2-4 seconds

, power reduction shall be confirmed when the 

1/2 power and night LED flashes 4 times. This function will 
help reduce fan noise in the short term, in the evenings, for 
example. The unit will revert back to full power after 8 hours 
automatically. Please note that night mode has to be set 
every single time you wish to use it. It can 

NOT

 be set to 

come on at a certain time daily. 

 Force Options

Regen timer adjustment: default 240 seconds 
(Regen low voltage timer time).

The default auto Regen time is 240 sec. = 4 min. 
The timer is prepped at 13.2V-19.0V on the input. 
If the input voltage then falls below 13.0V (x2 for 24V) 
the auto regen timer starts to count. If the voltage does
 not rise above 13.2V the timer will not reset and the unit 
will  switch  off,  however,  as  soon  as  the  voltage  rises 
above 13.2V the auto regen timer will automatically reset 
to the set value (default = 240sec).
To deactivate the auto regen mode set the auto regen time 
to 0 seconds.
By pressing the 

Setup / Enter 

only button for more than 10 

seconds you will enter the Auto Regen Time Setup. During 
the  whole Auto  Regen  Setup  the  “Absorption”  LED  will 
flash.
1. Absorption LED flashing and actual saved auto Regen 
time will be displayed on the right bar. Use the 0 to 840 
scale.  If  the  unit  is  out  of  the  factory  the  240  (default) 
should be displayed.
2. Press right button to increase or left button to decrease 
value.
3. To deactivate the auto regen function set timer value to 
0. When happy with your choice either wait 30 seconds or 
press both buttons at the same time for 2 seconds.
4. Absorption LED, AGM II and Auto Mode LEDs will flash 
10 times to confirm value saving. 
5. Unit will restart with new Auto Regen time as default and 
will remain there until changed again.

Important: 

If  you  have  changed  the  cutoff  voltage 

remember  that  the  auto  regen  counter  reset

  functions 

must see 0.2V on top of the new cutoff voltage.
I.e. You set the new cut off voltage at 14.0V. To reset 
the  Auto  Regen  timer  the  voltage  must  rise  above 
14.2V.

SVEM - Stationary Vehicle Engage Mode.

If your usage pattern is mostly stationary, e.g. You are at 
the side of the road and you start the vehicle just to run an 
inverter - the problem is that the vehicle’s alternator may 
only be at 13.1V (and not give a high voltage boost) and 
stay there, in this case the Pro Batt Ultra would not engage 
as it needs greater than  13.2V to start. The ideal solution 
is to have fitted the ignition feed mode (as per explained in 
these instructions). However, if the auto mode was used 
and the ignition feed had not been installed then you could 
use the 

Stationary vehicle engagement mode.

This mode allows the product to engage at a much lower 
voltage (13.1V) and disengage below (13.0V). To select 
this mode: Press SELECT button for 15+ seconds and let 
go, No Fault LEDs should be on solid and the Regen timer 
LED should be solid. To remove this setting then do the 
same again.

Warning:

 

  setting is 

the Stationary Vehicle Engage Mode

operating the unit at voltages which may cause problems 
in the winter to the starting of the vehicle.

10

0

0

0

1

1

0

1

0

1

Display software version

By  pressing  SELECT  for  10-15 
seconds certain LEDs on this column 
shall  briefly  illuminate  to  denote  the 
software  version  in  binary.  From  the 
top  ->  down  ‘

on

’  LEDs  =  1  and  ‘

off

’ 

LEDs = 0. 

For  example,  if  LEDs  8,7,5,3  are  on 
then the binary is 000110101 which, in 
decimals = 

53

. Use a calculator.

binary #

Turn off annoying buzzer

If the buzzer alarm is coming on and it annoys you, you 
can turn it off!. Please press the SELECT button down for 
40+  seconds.  This  shall  disable  the  buzzer  altogether, 
indefinitely.  You  can  reapply  the  buzzer  function  by 
repeating this procedure.

Содержание BB1230

Страница 1: ...e Float In Unit Out Rem Batt V 12 2 Temp Menu Change Volts Select Audible alarm on off hold 3 sec On Off hold 3 sec Fault Absorption Cond Optional Remote Instructions inside technology 4 DU L R A A T...

Страница 2: ...ustomise Operational Voltages Detailed Installation guide Page 8 Remote Control Operations Page 13 Operational m odes 1 2 3 Comprehensive breakdow n of remote functions Installation diagram Fault Find...

Страница 3: ...rrent limiting With fuses protecting the DC cables In a well ventilated dry dust free and condensation free environment When instruction manual has been read through Safety Symbols Example WARNING Nev...

Страница 4: ...tage if on solid it is high output voltage if flashing it is high input voltage 10 11 13 8 9 7 6 5 4 3 12 14 15 16 17 18 23 24 19 21 17 High temp trip if flashing then high unit temperature trip 18 No...

Страница 5: ...required Models BB1260 BB122470 BB123670 BB124870 BB242435 BB241235 Models BB1230 Front Panel II 8 2 3 4 7 10 11 12 13 9 5 14 5 3 4 BB122470 BB123670 BB124870 BB1260 BB242435 BB241235 4 60 73 00 4 60...

Страница 6: ...signal the BBC shall start charging again Use BMS 2 if your BMS trips to a ve voltage 2V 17V then use BMS 2 This shall result in the BBC turning off when this voltage is received Once the BMS removes...

Страница 7: ...2 seconds to confirm 2 x 3 sets of green LEDs shall flash to confirm Press Length s Action 0 1 Change to status fault display back to Voltage display mode 5 10 Toggles between 1 2 and 1 1 full power...

Страница 8: ...24V then the unit will simply start charging If the voltage drops below 13 0V the unit shall turn off With a caveat read on However if the input voltage has exceeded 13 2V 2x for 24V for 5 seconds the...

Страница 9: ...old both buttons for 30 seconds and let go The LED columns shall alternatively flash To confirm factory default press BOTH buttons again for 2 seconds Once confirmed 3 green LEDs on both columns shall...

Страница 10: ...auto regen timer starts to count If the voltage does not rise above 13 2V the timer will not reset and the unit will switch off however as soon as the voltage rises above 13 2V the auto regen timer w...

Страница 11: ...red custom values make a note Boost bulk absorption V ________ Conditioning V ________ Float V ________ AbsorptionTime Factor 0 18 ________ Absorption Minimum 0 960 minutes ________ Absorption Maximum...

Страница 12: ...ck mode constant voltage full current accessibility Stage 4 Backlash voltage If charger power exceeded and battery discharge unit resets to stage 1 Stage 5 Time Depending on battery size type state of...

Страница 13: ...e display shall read loc on number you have stored To remove loc return to loc and re enter the number Press select button and the display should read loc off green back light Please make a note of th...

Страница 14: ...ltage is 0 13V starter battery voltage then alternator may have failed Or requires increase rpm of engine possible belt slip Is your output voltage slightly higher or lower than expected even with no...

Страница 15: ...does not apply for shipping organised by yourself Please do not throw out any shipping or packaging materials All returns for any reason will require a proof of purchase with the purchase date The pr...

Отзывы: