INSTRUCTIONS

-

Position the charger in a cool, dry and well-ventilated space, ensuring a reasonable airflow around the 
charger. Do not install in a cupboard or in a sealed compartment.

-

Install as close to the batteries as possible, preferably within 2 metres of the batteries.

-

This unit is fitted with an automatic 110V/230V crossover switch. As such the following input voltage may be used : 
80V-130 V or 170V-280V at any frequency between 40Hz and 400 Hz.

-

The cable has to be at least 6mm² for 10amps to 20amps and 16mm² for 30amps. In case you have to install the 
unit further away from the batteries, increase the cable thickness to compensate for voltage drops in the line. (See 
Table 1.)

-

Before switching the charger on, it is important to set up the battery type. Please choose a battery type according to 
Fig.1. The charge rate (and voltage) will be highest for open lead-acid batteries (set to 14.8V/29.6V on high 
charge),  then  sealed/gel/AGM  batteries  (European  setting,  set  at  14.4V/28.8V)  and  then  gel/AGM  batteries 
(American setting at 14.2V/28.4V). AGM and gel voltages tend to vary among manufacturers, so please check 
which voltage your batteries require! Confirm that the L.E.D. indicates the correct battery type.

-

When different types of batteries are to be charged, the battery type with the lowest absorption voltage must be 
selected. Never charge a battery on a higher setting than it should!

-

The small set of 3 switches (Fig. 2) changes the time of the absorption charge by approx. 1 hour per switch. In order 
to set these switches divide the battery bank size by the amperage of the battery charger (e.g. a 20amp charger for 
a total battery bank of 200 amps hours would give you a ratio of 10.)

If the ratio is between 1 and 4, leave all switches “on” and the absorption time will be approximately 1 hour. This 

is ususally ideal for standard leisure boat use or livaboard use.

If the ratio is between 5 and 9, turn switch 1 “off” and the others “on”. The absorption time will be approximately 

2 hours. This is generally suitable for boats which use shore power only and which are used regularly, i.e. 
disconnected from shore power every day.

If the ratio is between 10 and 13, set switches 1 and 2 to “off” and switch 3 to “on”. The absorption time will be 

approximately 3 hours. Usually suitable for boats which use generators or shore power to charge the batteries 
about once a week.

For a ratio from 14 to 18 leave all switches in the “off” position for about 4 hours absorption time. Suitable for 

boats where batteries are charged mainly from generators and for all gel batteries.

-

Having set the battery type and the absorption time switches, the charger should be installed and will only need to 
be altered if there is a change in battery type or size.

-

Connect the cables as indicated in Fig 3. 

 Where only one 

battery is being charged, connect the surplus positive output terminals to the other used output terminal. This 
ensures correct regulation; failure to do this will reduce the charging performance.

-

The charger may be mounted in any position. Always connect the cables to the charger first, then run them to the 
batteries. Never connect any cables to the batteries before running them to the charger!

-

Warning:

 The charger case is earthed as per international regulations. On most boats, the A/C earth is connected 

to the bonding system and then to the negative of the battery. This means that the case could be negative. If a 
positive battery cables touches the case, this can set up a dead short to the battery negative via the earth cable and 
melt the earth cable; this could start a fire. To avoid this, ensure the battery connectors on the output studs do not 
touch the charger case. Use insulated output connectors. It is also recommended that all the charger outputs have 
a 50A fuse. (Sterling fuseholder GMFB-4848 not included.)

Always ensure that all the terminals are being used!

S

TERLING

Pro Charge

  

BATTERY CHARGER / POWER PACK

Fig. 1

Fig. 2

2

Содержание Pro Charge PT1210

Страница 1: ...logy 4 DU L A R T I A G B I L D E C D I E M S A I N G Y N D ProDigital RoHS compliant www sterling power com English Deutsch Fran ais Espa ol Italiano Nederlands Svenska Battery Chargers Power Packs P...

Страница 2: ...ure boat use or livaboard use If the ratio is between 5 and 9 turn switch 1 off and the others on The absorption time will be approximately 2 hours This is generally suitable for boats which use shore...

Страница 3: ...any damage The Float LED is on POWERPACK function Full current is available for on board supply STEP 4 RESET If the battery voltage goes down below 11 5V 23 0V then the charge cycle starts all over a...

Страница 4: ...e sch ma ci dessous Fig 3 Si vous n avez qu une batterie charger branchez sa borne positive tous les connecteurs du chargeur Cela permettra une charge optimale dans le cas contraire les performances d...

Страница 5: ...Elles peuvent ainsi rester connect es sans aucun risque de surcharge Le led Float est allum pendant cette phase POWERPACK Le chargeur est apte d livrer du courant au bateau sans avoir puiser dans les...

Страница 6: ...ine Ausgleichsladezeit von ca einer Stunde Diese Einstellung trifft h ufig f r kleinere Boote und f r Boote die oft und f r l ngere Zeit mit einem Landstromanschluss verbunden sind zu Bei einem Koeffi...

Страница 7: ...ohne Risiko einer berladung angeschlossen bleiben Die gr ne Float LED rechts leuchtet w hrend dieser Phase POWERPACK Funktion Das Ger t liefert die maximale Leistung zur Versorgung der an Bord eingesc...

Страница 8: ...mpo de absorci n ser de una hora aproximadamente Ideal para los barcos peque os o regularmente conectados al pont n Para una ratio comprendida entre 5 y 9 poner el switch 1 en off y los n mero 2 y 3 e...

Страница 9: ...te esta fase POWERPACK El cargador es apto para suministrar corriente al barco sin tener que utilizar las bater as FASE 4 RESET Si la tensi n de las bater as vuelve a 11 5V 23 0V el cargador reanuda s...

Страница 10: ...circuito e generare un inizio d incendio Per evitar ci assicuratevi che i connettori non siano in contatto con la custodia Si raccomanda d installare un fusibile 50A su ogni connettore atterie bisogn...

Страница 11: ...ase il led Float acceso POWERPACK Il caricatore pu erogare la corrente all imbarcazione senza attingerla dalle batterie FASE 4 RESET Se la corrente delle batterie scende al di sotto di 11 5V 23 0V il...

Страница 12: ...tijd zal ongeveer n uur bedragen Ideaal voor kleine boten of boten die regelmatig op het ponton aangesloten zijn Voor een ratio tussen 5 en 9 moet u switch 1 op off en 2 en 3 op on zetten De absorptie...

Страница 13: ...ndt de Float LED POWERPACK functie Wanneer de accuspanning op float spanningspeil gehouden wordt kan de lader stroom leveren aan de boot zonder zijn eigen accu s te moeten aanspreken FASE 4 RESET Wann...

Страница 14: ...an 1 och 4 placeras samtliga switchar p ON upptagningstiden blir ca en timme Idealiskt f r sm b tar eller de som regelbundet ansluts till pontonbryggan F r ett nyckeltal mellan 5 och 9 placeras switch...

Страница 15: ...er den Float leden POWERPACK funktion Laddaren kan leverera str m till b ten utan att beh va ta fr n batterierna FAS 4 RESET Om batteriernas sp nning sjunker under 11 5V b rjar laddaren om sin cykel i...

Страница 16: ...or replace the product if found defective within 30 days after return of the product to the company Sterling Power Products Ltd will ship the repaired or replaced product back to the customer This wa...

Отзывы: