![Stephill DSE 6110 MK3 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/stephill/dse-6110-mk3/dse-6110-mk3_user-and-fault-finding-manual_1372628008.webp)
Stephill Generators SSDP30-70 - DSE 6110 Module User Guide
Issue 2
How to Check Generator Frequency - Hz
Fig.11
Important Note
How to Check the Engine Instruments
Below are typical examples of each engine instrument screen - Fig.12 to Fig.17.
Engine Speed
Fig.12
Engine Oil Pressure
Fig.13
Engine Coolant Temperature
Fig.14
Cont.
The generator frequency can be found on two pages, on the
Status
page, as shown in Fig.3
Status
display.
Also the frequency has it's own instrument screen in the
Generator
page(s).
To access the frequency in the
Generator
pages, use the
Next
or
Previous
buttons until across the top of the
screen it reads
Generator
. Then press one of the
Instrument Scroll
buttons until
Generator Frequency
is
displayed at the top of the screen page Fig.11
The typical no-load frequency should be between
52.0
and
53.0 Hz
. If at no-load the frequency is as low as
51.5 Hz then it would be advisable to check the condition of the fuel filters, air filters and oil. Ensure the
engine is serviced regularly to safeguard the healthy running of the generator.
Most of the engine instruments will only be active once the engine is running. To check the engine
instruments press either the
Next
or
Previous
buttons until across the top of the screen it reads
Engine
.
Then press one of the
Instrument Scroll
buttons to scroll through all the engine instruments.
Generator Frequency
52.6
Hz
Engine Speed
1575
RPM
Engine Oil Pressure
4.88
bar
70
psi
488
kPa
Engine Coolant Temp.
82
⁰C
180
⁰F
Engine Battery Voltage
Next and Previous
Instrument Scroll
Next and Previous
Instrument Scroll
JD/08/18