Stephill Generators SSDP30-70 - DSE 6110 Module User Guide
Issue 2
How to Check the Generator AC Voltage is Correct
Note
Fig.6 below shows the typical no-load voltage between Phase and Phase L1-L2, L2-L3 and L3-L1.
How to Check If the Applied Current is Balanced
An unbalanced current can cause the generator voltages to become unstable and possibly shutdown the set.
Fig.7
Important Note
To check the current applied to the generator use the
Next
or
Previous
buttons until across the top of the
screen it reads
Generator
. Then press one of the
Instrument Scroll
buttons until
Generator Current
is
displayed at the top of the screen Fig.7
Ensuring the current on each phase is as even (balanced) as possible will eliminate nuisance
Over Current
or
Over/Under Voltage
shutdown alarms.
If the page automatically scrolls to another, press either of the
Instrument Scroll
buttons
until you reach the desired page
Fig.6
Fig.5
The first page will show the AC voltage between each phase (L1,L2 and L3) and Neutral (when generator
running) Fig.5
To check the AC voltage output from the generator is correct, firstly you must isolate the
load from the generator (remove any AC plugs connected to the generator outputs). Either
before you start the generator or while the generator is running, use the
Next
or
Previous
page button until across the top of the screen it reads
Generator
.
Generator Voltage
L1 - N
231
V
L2 - N
L3 - N
231
V
230
V
Generator Voltage
L1 - L2
401
V
L2 - L3
L3 - L1
400
V
400
V
Generator Current
L1
17
A
L2
L3
19
A
15
A
Next and Previous
Instrument Scroll
JD/08/18