Stephill Generators SSDP30-70 - DSE 6110 Module User Guide
Issue 2
How to Reset the "Service Hours Alarm " Warning
Before Resetting the Service Hours
Resetting the Service Hours
Fig.21
a) Ensure the
Service Hours
screen is visable.
b) Press and hold the button. The timer should then reset to the pre-set hours (usaully 500h).
Important Note
The
Service Hours
timer can only be reset if the
Service Hours Warning
has been activated (reached 0h 0m).
How to Check Which Alarms Have Been Triggered
When an alarm is active, the
Internal Audible Alarm
sounds
.
The audible alarm is silenced by pressing the Alarm Mute / Lamp Test button.
Fig.22
① = Number of active alarms. This is alarm 1 of a total of 2 active alarms.
② = The cause of the alarm.
③ = The type of alarm, e.g. Shutdown.
Firstly you will need to access the
Service Hours
in the
Engine
pages, use the
Next
or
Previous
buttons until
across the top of the screen it reads
Engine
. Then press one of the
Instrument Scroll
buttons until
Service
Hours
is displayed at the top of the screen page Fig.21
The
Service Hours Alarm
screen is a count down timer, when the timer reaches zero hours a
Warning Alarm
will be issued and displayed on the screen. The
Warning Alarm
will allow the user to operate the generator
as normal but the
Warning Alarm
will be present until a service reset has been performed.
Firstly, ensure an adequate service has been performed on the engine. Refer to the generator handbook or
check on the
Service
section found on;
The
Service Hours
should be showing 0h 0m, this idicates that the countdown timer from the last service has
been achieved. To reset this timer;
To check which alarm(s) have been triggered, use the
Next
or
Previous
buttons until across the top of the
screen it reads
Alarms
. Fig.20 shows the
Alarms
page. To see each individual alarm that is currently
activated, press one of the
Instrument Scroll
buttons to cycle through.
Emergency Stop
Shutdown
2/2
Alarms
www.stephill-generators.co.uk
Service Hours
0h 0m
Next and Previous
Instrument Scroll
③
①
②
Next and Previous
Instrument Scroll
JD/08/18
10