Stephill Generators SSDP30-70 - DSE 6110 Fault Finding Guide
Issue 3
• Check E-stop has not been pressed in.
• Check E-stop switch wires are not loose.
• Check oil level and fill to the correct level if necessary.
• Oil switch fault - see below.
• Oil sender fault - see below.
• Check for continuity between the oil switch body to the engine earth.
• Replace oil sender.
• Check connections at the oil sender
• Check continuity between wire No.16 on the DSE 6110 to the oil sender.
• Check continuity between wire No.15 on the DSE 6110 to engine earth.
• Check continuity between wire No.1 on the oil sender to engine earth.
• Replace oil sender.
• Check for loose wires on the oil switch.
• Check continuity between wire No.43 from the DSE 6110 to the oil switch.
• Replace oil switch.
Oil Pressure Low
Switch
Fail to stop
could indicate a faulty oil pressure switch!
• Check oil pressure switch and pipework - remove & clean -
Oil & filter change would be
advisable.
Continued
Oil Pressure Shutdown
Fault operates after the
engine has fired.
Oil Pressure Low Sender
(####)
Fault Condition
Fail to Stop
Alarm after 1 to 2
minutes when engine is at
rest.
Emergency Stop
Shutdown
Common Fault Conditions
Below is a general guide for the most common fault conditions on a Stephill Generator using a DSE 6110 Mk3 control
module.
Checks & Tests
• Check wiring is not open circuit - check for continuity between each side of the switch on the
back of the E-stop.
• Check that both wires on the E-stop have continuity to the corresponding positions on the
back of the DSE 6110 - wire No.2 & 3.
• Check that 12V is present across between position 3 and 1 on the back of the DSE 6110
module.
• Check engine oil pressure when running. On the DSE 6110
Engine
page. (2 to 5 bar is normal)
• Check oil pressure sender and switch assembly including pipework - remove & clean -
Oil &
filter change would be advisable.
• Check continuity between wire No. 43 on the oil switch to the DSE 6110 module (remove from
oil switch to test).
• To test the oil pressure switch first remove wire No.43 and link this wire to a clean earth point
on the engine. Start the generator, as soon as the engine starts to run remove the wire No.43
from the earth point. If the generator continues to run then this would indicate that the wiring is
good and the fault could possibly be the oil pressure switch.
• Check oil pressure sender and pipework - remove & clean -
Oil & filter change would be
advisable.