Stephill Generators SSDP30-70 - DSE 6110 Module User Guide
Issue 2
Generator Locked Out
to scroll to the alarms page to investigate.
Status Display
①
③
②
Fig.3
Typical No-Load Values
Fig.3 above is showing the typical no-load (nothing connected to the generator outputs) values.
②
=
L-L
is showing the average AC voltage between phases, L1 to L2, L2 to L3 and L3 to L1 - 400V
③ =
Showing the alternator frequency -
Hz
- This should be between 52.0 to 53.0 at no-load.
Typical Load Values
When you apply load the generator the
Status
screen will then show the following - Fig.4
①
②
③
Fig.4
① =
Is showing the average amps between all three phases (Live).
②
= Is showing the total load in kW that the generator is under.
③ =
Is showing the alternator power factor - pf cosφ.
If
Generator Locked Out
is displayed on the screen - Fig.2 then this indicates that the generator cannot be
started due to an active
Shutdown
on the module.
Once you have issued a start request and the generator has started and running, the DSE 6110 MK3 module
will then begin checking that the engine instruments and the AC generator output are correct and are within
the pre-set parameters. After the "
Saftey on Delay
" of 10 seconds has elapsed and all is operating correctly,
the
Status
screen will typically look like the following Fig.3.
① =
L-N
is showing the average AC voltage between (Phase or Live) L1 to Neutral, L2 to Neutral and L3 to
Neutral - 230V
Press the
Next
and
Previous
page button
Press the Stop/Reset Mode button to clear the alarm, if
the alarm does not clear the fault is still active.
400V
Generator Available
L - N
0 A
0 kW
- - - - pf
L - L
230V
52.6 Hz
Status
12:34
Generator Locked Out
Fig.2
400V
Generator Available
L - N
17 A
12 kW
1.00 pf
L - L
230V
51.9 Hz
JD/08/18
5