Stephill Generators SSDP30-70 -  DSE 6110 Module User Guide

Issue 2

Generator Locked Out

to scroll to the alarms page to investigate.

Status Display

Fig.3

Typical No-Load Values

Fig.3 above is showing the typical no-load (nothing connected to the generator outputs) values.

 = 

L-L

 is showing the average AC voltage between phases, L1 to L2, L2 to L3 and L3 to L1 - 400V

③ =

 Showing the alternator frequency - 

Hz

 - This should be between 52.0 to 53.0 at no-load.

Typical Load Values

When you apply load the generator the 

Status

 

screen will then show the following - Fig.4

Fig.4

① =

 Is showing the average amps between all three phases (Live).

 = Is showing the total load in kW that the generator is under.

③ =

 Is showing the alternator power factor - pf cosφ.

If 

Generator Locked Out

 is displayed on the screen - Fig.2 then this indicates that the generator cannot be 

started due to an active 

Shutdown 

on the module.

Once you have issued a start request and the generator has started and running, the DSE 6110 MK3 module 
will then begin checking that the engine instruments and the AC generator output are correct and are within 
the pre-set parameters. After the "

Saftey on Delay

" of 10 seconds has elapsed and all is operating correctly, 

the 

Status

 screen will typically look like the following Fig.3.

① =

 

L-N

 is showing the average AC voltage between (Phase or Live) L1 to Neutral, L2 to Neutral and L3 to 

Neutral - 230V

Press the 

Next

 and 

Previous

 page button 

Press the Stop/Reset Mode                button to clear the alarm, if 
the alarm does not clear the fault is still active.

400V 

Generator Available 

L - N 

0 A 

0 kW 

- - - - pf 

L - L 

230V 

52.6 Hz 

Status 

12:34 

Generator Locked Out 

Fig.2 

400V 

Generator Available 

L - N 

17 A 

12 kW 

1.00 pf 

L - L 

230V 

51.9 Hz 

JD/08/18

5

Содержание DSE 6110 MK3

Страница 1: ...Issue 3 June 2020 SSDP30 70 Range DSE 6110 MK3 Control Module User Fault Finding Guide...

Страница 2: ...e Load Applied is Balanced and the Total Load How to Check the Generator Frequency How to Check the Engine Instruments Engine Speed Engine Oil Pressure Engine Coolant Temperature Engine Battery Voltag...

Страница 3: ...f the DSE6110 MK3 module as configured on Stephill Generators and to gain access to the information available It has been produced as a How to guide Once the 12V supply has been connected to the modul...

Страница 4: ...on removal of the start signal the generator will stop It is possible to scroll to display the different pages of information by repeatedly operating the Next and Previous page buttons Once selected t...

Страница 5: ...is displayed on the screen Fig 2 then this indicates that the generator cannot be started due to an active Shutdown on the module Once you have issued a start request and the generator has started and...

Страница 6: ...ven balanced as possible will eliminate nuisance Over Current or Over Under Voltage shutdown alarms If the page automatically scrolls to another press either of the Instrument Scroll buttons until you...

Страница 7: ...buttons until across the top of the screen it reads Generator Then press one of the Instrument Scroll buttons until Generator Load is displayed at the top of the screen Fig 9 Standby kW Is the maximum...

Страница 8: ...nerator Frequency is displayed at the top of the screen page Fig 11 The typical no load frequency should be between 52 0 and 53 0 Hz If at no load the frequency is as low as 51 5 Hz then it would be a...

Страница 9: ...running or at standstill you will see one of two screens showing the current fuel level Fig 18 Fig 19 shows no registered fuel level this is the fuel level screen when the generator is at standstill n...

Страница 10: ...Instrument Scroll buttons until Service Hours is displayed at the top of the screen page Fig 21 The Service Hours Alarm screen is a count down timer when the timer reaches zero hours a Warning Alarm...

Страница 11: ...t to change with module updates To view the Event Log use the Next or Previous buttons until at the top of the screen it reads Event Log Fig 23 press one of either the Instrument Scroll buttons to vie...

Страница 12: ...hutdown Common Fault Conditions Emergency Stop shutdown Low Oil Pressure shutdown Oil Pressure Sender Sender Fault shutdown Fail To Stop High Engine Temperature shutdown Coolant Level shutdown Charge...

Страница 13: ...module STEPHILL GENERATORS LTD STRESS THAT THE ULTIMATE RESPONSIBILTY FOR THE SAFE USE OF THE GENERATOR RESTS WITH THE USER Recommended Checks Before Attempting Any Fault Finding Before starting the g...

Страница 14: ...reen on the DSE 6110 module user guide page 4 Start the generator and check that all the voltages displayed are correct If there is an large imbalance of voltages then check the following The module d...

Страница 15: ...rap filter It maybe also worth checking the air filter s are in good condition replace is necessary If the above fails to raise or rectify the issue it may be worth checking the engine for possible ma...

Страница 16: ...rest Emergency Stop Shutdown Common Fault Conditions Below is a general guide for the most common fault conditions on a Stephill Generator using a DSE 6110 Mk3 control module Checks Tests Check wirin...

Страница 17: ...agnetic connection behind the hardwire door and control box Check wiring from the switch to the DSE 6110 wire No 46 Check switch operation Open from ground to fault Check all MCCB MCB s are in the ON...

Страница 18: ...k Fuel pump operational press and hold the prime button if applicable 12V present between wires 51 1 on the fuel pump plug when the prime button is pressed Replace 12V fuel lift pump Yes Disconnect th...

Отзывы: