DIP 6 / 7 / 8

Trigger mode

The trigger mode enables the user to choose which sensing technologies  

should be used to initially turn the load on and which technologies are  

required to keep it on. The following settings are possible:

Both:  

Requires movement recognition by PIR and US

Either:   Requires movement recognition by PIR or US

PIR:  

Requires movement recognition by PIR

US:  

Requires movement recognition by US

Initial occupancy:

Sensor technology used to turn the load on (PIR, US, Both, Either)

Maintain Occupancy:

Sensor technology used to keep the load on after initial occupancy (PIR, US, Both, Either)

The trigger mode is selected by DIP switches 6, 7 & 8.

 

COM 1 + COM 2 

DIM

Trigger mode options 

n

Initial Occupancy

Maintain Occupancy

DIP

6

DIP

7

DIP

8

Option 1 (factory setting)

Both

Either

OFF

OFF

OFF

Option 2

Both

Both

OFF

OFF

ON

Option 3

PIR

Either

OFF

ON

OFF

Option 4

US

Either

OFF

ON

ON

Option 5

Either

Either

ON

OFF

OFF

Option 6

US

US

ON

OFF

ON

Option 7

PIR

PIR

ON

ON

OFF

Option 8

Either

Both

ON

ON

ON

on

 

1 2 3 4 5 6 7 8

TEST

MODE

MANUAL

ON / OFF

NOT 

USED

NORMAL

MODE

AUTO

ON

NOT 

USED

TRIGGER MODE 

(IR CM NOT USED)

on

 

1 2 3 4 5 6 7 8

TEST

MODE

MANUAL

ON / OFF

CONST.

OFF

NORMAL

MODE

AUTO

ON

CONST.

ON

TRIGGER MODE 

(IR CM NOT USED)

Functions – Settings by Potentiometer

Application Examples

Light level settings

Night-time mode, minimum setting approx. 10 lux / 1 fc

min 

Corridors, foyers

1

Stairs, escalators, moving walkways

2

Restrooms, dining areas

3

Classrooms, sales floors, gymnasiums

4

Individual offices, conference and meeting rooms

5

Laboratories, precision work areas

>=6

Daylight mode

max 

The occupancy time delay  

setting for switching output 1  

is adjustable from a minimum  

of 30 seconds to a maximum of  

30 minutes.

Occupancy time delay setting

If the dial is set to 

 (fully coun-

terclockwise), the unit is in pulse 

mode, i.e. the output is switched 

'ON' for approx. 2 sec. Afterwards, 

the sensor does not respond to 

movement for approx. 8 sec.  

For use with a time delay relay.  

(Not available with the DIM-24 

sensors).

Turned fully clockwise: The stay-

'ON' time is self-learning and  

adjusts dynamically to user  

behavior. The optimum time  

cycle is determined by means of  

a learning algorithm. 

The shortest time is 5 min.,  

the longest 20 min. 

Pulse mode (except DIM) 

IQ mode

The chosen response threshold 

can be adjusted from approx.  

10 – 1000 lux / 1 – 100 fc.

Control dial turned fully clockwise: 

MAX daylight mode

Control dial turned fully  

counterclockwise:  

MIN night-time operation

Light level setting

Potentiometer 

e

Potentiometer 

f

Note: Depending on the site of installation, the setting may need to be corrected by 1 – 2 marks on the scale.

Brightness is measured directly at the sensor.

Sensor DIP Switch Settings

d

US

Содержание DT CM COM1-24

Страница 1: ...DT CM COM1 24 DT CM COM2 24 DT CM DIM 24 IR CM COM1 24 IR CM COM2 24 IR CM DIM 24 Information E FR US FR US ES...

Страница 2: ...a round 3 0 mud ring k Mounting plate a a Ceiling mount adapter b Sensor b Can be mounted directly to the ceiling or wall using anchor bolts or can be mounted to the ceiling using the supplied 1 2 sn...

Страница 3: ...DETECTION 0 10 10 20 20 30 30 40 40 50 50 60 60 70 70 80 80 90 90 91 78 65 52 39 26 13 0 91 78 65 52 39 26 13 ft m 28 24 20 16 12 8 4 0 28 24 20 16 12 8 4 PIR RADIAL DETECTION 0 10 10 20 20 30 30 40...

Страница 4: ...ft 10 m 82 ft 9 ft 3 m 25 m 26 ft 8 m 16 ft 5 m 10 ft 160 Recommended Application l DT CM Only IR CM COM1 24 DT CM COM1 24 Occupancy time delay setting See page 21 Ultrasonic reach setting See page 22...

Страница 5: ...HVAC switch ON delay See page 22 h Sensor DIP switch settings See page 18 19 20 Ultrasonic transducers DT CM Only c IR CM DIM 24 DT CM DIM 24 DT CM Only e f m d Light level setting See page 21 Occupan...

Страница 6: ...d options available to you with these devices This will also assist you to minimize installation time and provide maximum energy savings and trouble free operation Safety Warnings l How it Works Basic...

Страница 7: ...y Momentary Switch Optional LineVoltage Maintained Contact Switch Optional LineVoltage Maintained Contact Switch Blue Control Black 24VDC Red 24VDC Gray Momentary Switch COM2 24 Wiring 10 2 Note Power...

Страница 8: ...4 VDC Red 24 VDC Green Switch Input Brown Communication HVAC Yellow Red Normally Open HVAC Yellow Relay Common HVAC Yellow Black Normally Closed HVAC Yellow Red Normally Open HVAC Yellow Relay Common...

Страница 9: ...50 60Hz DTCMDIM 24 18 24VDC VAC 39mA 50 60Hz Maximumload Controloutput Blue 1A 24VDC VAC50 60Hz Controloutput Blue 1A 24VDC VAC50 60Hz HVACdrycontacts Common Yellow Normallyopen Yellow Red 1A 24VDC VA...

Страница 10: ...detector as a manual on unit or override it manually at any time When using the IR CM DIM 24 or DT CM DIM 24 and a momentary switch light can be dimmed manually by pressing and holding the momentary...

Страница 11: ...y Potentiometer Application Examples Light level settings Night time mode minimum setting approx 10 lux 1 fc min Corridors foyers 1 Stairs escalators moving walkways 2 Restrooms dining areas 3 Classro...

Страница 12: ...C 8 service remote commissioning tool gives the installer the ability to set basic functions of the entire line of Control Pro sensors via remote control Each valid press of a button is indicated by a...

Страница 13: ...nd 0 10 volt dimming ballasts The last light level adjustment setting is saved and will return after being switched OFF and then back ON again by the RC 4 switch or presence detection Light ON OFF The...

Страница 14: ...s time delay or use with a time delay relay Malfunction Cause Remedy Warranty Steinel America Inc warrants its products against defects in material or workmanship for a period of five years STEINEL w...

Страница 15: ...ixation au plafond o Boulons d ancrage p crou de blocage et rondelle p Manchon de travers e de 1 2 po 1 27 cm Positionnement Zone de d tection l Positionnement R glages Au centre du mur 8 pieds 2 4 m...

Страница 16: ...50 60 60 70 70 80 80 90 90 40 91 78 65 52 39 26 13 0 91 78 65 52 39 26 13 ft m 28 24 20 16 12 8 4 0 28 24 20 16 12 8 4 D TECTION PIR TANGENTIELLE 0 10 10 20 20 30 30 40 40 50 50 60 60 70 70 80 80 90 9...

Страница 17: ...pages 43 44 et 45 Transducteurs ultrasons uniquement DT CM c DT CM Only 15 IR CM COM2 24 DT CM COM2 24 R glage de la luminosit Voir page 46 R glage de la tempori sation de la pr sence Voir page 46 R...

Страница 18: ...nt pour le d tecteur DT CM e R glage de la luminosit f R glage de la temporisation de la pr sence Sortie de commutation 1 g Dur e de MARCHE de la CVC Sortie de commutation 2 h Temporisation de MARCHE...

Страница 19: ...de d clenchement uniquement DT CM IR CM DIM 24 DT CM DIM 24 1 sortie de commutation de basse tension fonctionnant en pr sence d un mouvement et en fonction de la luminosit ambiante Une sortie de varia...

Страница 20: ...r multiple 10 3 Remarque le pack d alimentation doit tre en mode auto D autres sch mas de c blage sont disponibles sur notre site Internet www steinel net IR CM COM2 24 DT CM COM2 24 Un c ble 18 AWG e...

Страница 21: ...10V C blage de DIM 24 d tecteur multiple 10 5 IR CM DIM 24 DT CM DIM 24 Un c ble 18 AWG est recomman d pour un branchement basse tension entre les d tecteurs et les packs d alimentation Les lignes se...

Страница 22: ...mode impul sions pas d ARR T manuel possible Il n est pas possible d TEINDRE manuellement la lumi re dans le r glage MARCHE La dur e de MARCHE recom mence au d but chaque fois que vous appuyez sur la...

Страница 23: ...nce humaine la lumi re s ALLUMERA imm diate ment au dernier niveau d intensit s lectionn Option de commande du niveau de la luminosit constante DIM MARCHE ARR T R glages des commutateurs DIP du d tect...

Страница 24: ...CVC auto r duit la sensibili t de la sortie de commutation Pr sence Le contact ne se ferme qu apr s avoir examin l activit de l espace et avoir signal avec un haut degr de certitude que plu sieurs per...

Страница 25: ...atiquedelatemporisationde miseen MARCHE apr squedespersonnesse sonttrouv esdanslazoneded tection Aucunetemporisation Temporisationde10min Modeder glageduseuildelumin ded clenchement r glageenusine Ile...

Страница 26: ...tecteur s TEINT en cas d occupation Le d tecteur ne s TEINT pas assez rapidement Le capteur d tecte la pr sence initiale mais s teint en l espace de 2 secondes L Pas de tension d alimentation L R gla...

Страница 27: ...de montaje a a Adaptador para montaje en techos b Sensor b Puede montarse directamente en el techo o la pared empleando tornillos de anclaje o montarse en el techo empleando el empalme roscado para en...

Страница 28: ...0 70 80 80 90 90 91 78 65 52 39 26 13 0 91 78 65 52 39 26 13 ft m 28 24 20 16 12 8 4 0 28 24 20 16 12 8 4 DETECCION RADIAL PIR 0 10 10 20 20 30 30 40 40 50 50 60 60 70 70 80 80 90 90 91 78 65 52 39 26...

Страница 29: ...9 ft 3 m 25 m 26 ft 8 m 16 ft 5 m 10 ft 160 Aplicaci n recomendada l DT CM Only IR CM COM1 24 DT CM COM1 24 Temporizaci n de la presencia V ase p gina 71 Ajuste del alcance ultras nico V ase p gina 7...

Страница 30: ...conexi n V ase p gina 72 h Ajustes del conmutador del DIP sensor V ase p ginas 68 69 70 Transductores ultras nicos solo DT CM c IR CM DIM 24 DT CM DIM 24 DT CM Only e f m d Ajuste de nivel de luz V a...

Страница 31: ...arizarse con todas las funciones y opciones que este dispositivo le ofrece Esto adem s ser til para mini mizar los tiempos de instalaci n y para conseguir el m ximo ahorro de energ a y perfecta operat...

Страница 32: ...4VDC Rojo 24VDC Gris conmut moment neo Conmutador de alimentaci n permanente opcional Conmutador de alimentaci n permanente opcional Azul control Negro 24VDC Rojo 24VDC Gris conmut moment neo Cableado...

Страница 33: ...t Marr n comunicaci n CEA amarillo rojo normalmente abierto CEA amarillo rel tierra CEA amarillo negro normalm cerrado CEA amarillo rojo normalmente abierto CEA amarillo rel tierra CEA amarillo negro...

Страница 34: ...M2 24 18 24VDC VAC 40mA 50 60Hz DTCMDIM 24 18 24VDC VAC 39mA 50 60Hz M ximacarga Salidadecontrol azul 1A 24VDC VAC50 60Hz Salidadecontrol azul 1A 24VDC VAC50 60Hz ContactossecosCEA tierra amarillo Nor...

Страница 35: ...ctivar un automatismo ma nualmente en cualquier momento Utilizando el IR CM DIM 24 o DT CM DIM 24 y un conmutador moment neo la luz puede gra duarse manualmente apretando y manteniendo apretado el con...

Страница 36: ...USADO Funciones Ajustes mediante potenci metro Ejemplos de aplicaci n Ajustes de nivel de luz Modo nocturno ajuste m nimo aprox 10 lux 1 vela m n Pasillos recibidores 1 Escaleras escaleras mec nicas p...

Страница 37: ...ante potenci metro Ajuste vertical alcance PIR Descripci n El mando a distancia de servicio RC 8 herramienta de puesta en funcionamiento capacita al instalador para ajustar funciones b sicas de la com...

Страница 38: ...onexi n v a Bluetooth con smartphones and tablets APP para iOS y Android Guardar cargar ajustes para la instalaci n f cil tipo copiar y pegar Descargar la APP Emparejar v a Bluetooth Listo para el uso...

Страница 39: ...Reducir el nivel de luz L Reducir la temporizaci n L Reajustar la zona de alcance L Aumentar la temporizaci n L Regular umbral de luz L Reducir la temporizaci n L Ajustar la temporizaci n del sensor o...

Отзывы: