5
738.955 | 10.40
EN
Speed
control
"oFF":
Control
signal
as
switched
out-
put
When switched on, the solar circuit pump runs at
maximum speed (100 %) and delivers a constant vol-
ume flow.
Speed
control
"on":
Control
signal
speed
controlled
When switched on, the solar circuit pump runs at a
controlled speed in the range of 30 ... 100 % and deliv-
ers a regulated volume flow.
The following display appears:
The speed control symbol is displayed
The speed control function, however, makes a distinc-
tion between the "differential temperature control"
and "absolute temperature control":
Differential
temperature
control
"diF"
:
The control system attempts to maintain a
constant temperature difference between the
collector and the storage tank. The solar circuit
pump performance is continuously adjusted and
the volume flow is increased or reduced, depend-
ing on the temperature difference. The specified
temperature difference is fixed at 8 K.
Absolute
temperature
control
"AbS“
The solar circuit pump is controlled in such a
manner that the collector temperature sensor
T1 is kept at the absolute temperature as con-
stantly as possible so that the storage tank can
•
-
-
T1
T1