7
735.794 | 10.10
EN
Slide the locking clip upwards again, so that the unit is
retained to the bottom rail. The unit is now fixed in place.
Plug the AC connectors into the inverter (right hand
side). If there is only one inverter, the AC connector is
not required.
Position the next inverter on the rail and connect it to
the first one.
Repeat steps to 4 until the system reaches the desired
size (max. of 3,600 Watts AC power).
WARNING!
Risk of death by electrocution!
Do not touch bare cable ends.
Disconnect cables from the solar module before cutting
them to size.
Connect the cables from the solar module (DC cable)
via an external DC switch to the direct current input of
the inverter.
Make sure the + / - wires are connected to the plugs
correctly (male/female) and correctly coded. The ne-
gative connection terminal on the inverter is always
closest to the wall.
If there is an adequate supply of sunlight, the inver-
ters will switch to the ‘Stand-by’ mode: this is indica-
ted when the LED flashes.
As the mains supply has not yet been connected, the
inverter will not generate an output voltage.
WARNING!
Risk of death by electrocution!
The unit may only be connected to the grid by qualified
personnel in accordance with the regulations of the local
power supply company.
Connect a mains connection cable to the right hand
side of the inverter. Connect the inverters to the mains
grid. When there is sufficient sunlight, the inverters will
begin to feed electricity into the grid and the LED will
light up permanently.
33
44
55
66
77