O P E R A T I O N & S E R V I C E
Control configuration
Touch pad control allows you to change the mode of control for the humidifier.
Push on the ‘’settings mode’’ button on the touch pad controls – When
steamOres
is in setting mode the
blue LED located beside this button will turn ON.
Caution
: Risk of malfunction, change of mode should not be done without checking which control
signal is connected to the steamOres. Incompatible mode selection and signal wiring can lead to
malfunction.
The mode selection is done and indicated by the 5 LEDs and +/- buttons located on the left hand side of
the touch pad control. Here below are the available modes:
Modes
#1
#2
#3
#4
#5
#6
External demand
(0-10Vdc)
RH%
Internal set-point
Temperature
(0-10Vdc)
On/Off
contact
Modbus Temperature
(PT1000)
5 LEDs
indications
off
off
off
off
ON
off
off
off
ON
off
off
off
off
ON
ON
off
off
ON
off
off
off
off
ON
off
ON
off
off
ON
ON
off
Where to
connect
Schematic
#1
Schematic
#2
Schematic
#3
Schematic
#4
Schematic
#5
Schematic
#6
Set point
adjustment
with RES
touch pad
No
Yes
(20-70%RH)
5% per step
10% per LED
Yes
20-70%°C
[68-158°F]
5°C per step
10°C per LED
No
No
Yes
20-70°C
[68-158°F]
5°C per step
10°C per LED
Schematic #1
Schematic #2
Schematic #3
Gnd
Analog demand
0-10Vdc
RH / AD
+
-
Optional 24Vdc output
+
+
-
PT1000-2
Schematic #4
Schematic #5
Schematic #6
HLH
EN-C
Enable ON/OFF contact
Optional outside power source
(24Vdc) for enable contact
sh7
RS485
U
SB
Power
Health
Steam
Alarm
Service
A+
B-
Gnd
Modbus
connection
Demand to be sent to holding
register 36
23
Gnd
24Vdc
RH% signal
RH%
sensor
PT1000-2
RH / AD
Signal from RH% sensor
+
+
-
Gnd
24Vdc
Temp. signal
Temp
sensor
PT1000-2
RH / AD
Signal from Temp sensor
+
+
-
PT1000
PT1000-2
RH / AD
+
+
-
+
+
-