I N S T A L L A T I O N
Installation – step 3 - Drain installation
Water drained specification:
Drained water maximum temperature: 140°F [60°C] (
when supplied with cold water supply)
Drained water flow rate: 2.6 GPM [10 L/min]
Drain outlet dimension: 1in [DN25]
Drain
P trap
12in
[30cm]
Drain Outlet
Diam. 1in [DN25]
Slopped drain line
rigid or flexible (by others)
Building drain
open and deported from humidifier
Figure 8 – water drain connection
Installation steps :
1. Ensure that an Open drain with a P-trap is installed offset from the
steamOres
humidifier.
2.
IMPORTANT
: Risk of malfunction. A minimum
slope angle
of 5 degree of the drain hose or pipe
and a minimum length of 8in [20cm] must be provided between the drain outlet of the
steamOres
humidifier and the open drain inlet.
3. A minimum of 12in [30cm] vertical run before P trap or obstruction must be provided
14