I N S T A L L A T I O N
18
Installation – step 2
Water supply installation
Water supply specification & quality:
Water supply pressure: 15 to 80PSI [1 to 5bar]
Water supply temperature: 37 to 105°F [3 to 40°C]
IER electric steam humidifier can accept a wide range of water quality.
Untreated water will lead to scale deposits that will need to be regularly removed from steam
chamber.
Use of additives such as scale inhibitor or corrosion inhibitors, disinfectants or other can impair
the normal operation of the humidifier and are not allowed.
Water supply conductivity: 1 to 1500
µ
S/cm
Water supply hardness: 0 to 16grains/gallon [0 to 15°gH][268mg CaCO
3
/l]
Water supply PH: 6.5 to 7.5
Water supply chloride content: 0 to 50ppm
Figure 11 – water supply connection