background image

CP-1 CONTROL PACKAGE

Install the cable from the area of  the Tem-
perature Sensor (Probe) to the steam
generator’s location. The Temperature Sen-
sor (Probe) MUST be located inside the
steamroom. In steamrooms with singletier
seating the Sensor should be located 6 feet
above the floor, with two tier seating it should
be 7 feet above the floor and in either case
away from the steamhead and steamroom
door. The connector end of the wire must be
installed inside the steamroom. 

NOTE

: A

5/8 inch hole should be provided so that the
connector can be passed through the wall for
installation found later in these instructions.

2)

CP-1 System Control Package Installation

Temperature Sensor (Probe ) (for installation
inside the steamroom)

C. 1)

Locate the 2 wire cable described in the
Rough-in section.

a.

Keeping the 5/8 inch hole centered, drill two
1/4 inch holes 2 inches apart. Insert 2-No. 8
plastic anchors into drilled holes.

b.

c. Follow Figure 3.

Temperature Control Panel (for installation out-
side the steamroom )

2)

Attach the 3 wires (P1, P2, and P3) from the
Temperature Control Potentiometer to the 3
wire cable in the two-gang box. Note the
colors of wire P1, P2, and P3 are attached to
match the colors of the 3 wire cable to the
potentiometer wire colors.

a.

Secure Temperature Face Plate to the two-
gang box using four (4) machine screws. (See
Figure 4.) 

Important:

 Care must be taken

to mount Temperature Face Plate properly.

b.

5

Содержание HC-10

Страница 1: ...HEAVY COMMERCIAL STEAMBATH GENERATOR OWNERS MANUAL Models HC 9 Thru HC 18 3 98 Pub No 400 G ...

Страница 2: ...Auto Blowdown and Automatic ON OFF Time Clock 8 V Steam Generator Operation 8 VI Steam Generator Maintenance 8 A Manual Blowdown 8 B Periodic Inspection 8 LIST OF ILLUSTRATIONS 1 Dimensional Drawing for Heavy Commercial Steam generator HC 9 thru HC 18 1 2 Typical Steam generator Installation 3 3 ST 200C Temperature Sensor Installation 4 4 ST 200C Temperature Control Installation 5 5 System Control...

Страница 3: ...r your steamroom 1 2 3 the steamhead Insulate the steam pipe The serial number plate should be vis ible Refer to Figure 2 for Installation drawing Do not Install outdoors or an area where parts may freeze or corode Also do not install near combustible materials i e paints thinners chlorine etc The steamroom must be completely sealed on all sides top and bottom Floor walls and ceiling should be com...

Страница 4: ...nect the steam line from the preViously roughed in location to the steam solenoid valve on the generator marked steam out let See Figure 1 1 2 3 4 In the steamroom place the center of the escutcheon onto the steam pipe and Screw the stearnhead into place Care must be taken not to Scratch the stearnhead or es cutcheon with a wrench Be Sure the steam slot in the stearnhead is facing down After the p...

Страница 5: ...TALLATION Replace cover and secure screws removed in step 1 6 NOTE Steam Generator will not operate without water 3 If connections are made properly the indi cator lamp will illuminate when the 7 generator is heating ...

Страница 6: ...e INSIDE the steamroom WARNING All electrical power to the steam gen erator MUST be turned OFF before proceeding with installation B CP 1 Control Package Rough in The 3 wire cable for Temperature Control Panel to be used during installation of the ST200C Solid State Temperature Control System is low voltage 18 or 22 AWG wire recommended Every attempt should be made to match the color wire of the T...

Страница 7: ...instructions 2 CP 1 System Control Package Installation Temperature Sensor Probe for installation inside the steamroom C 1 Locate the 2 wire cable described in the Rough in section a Keeping the 5 8 inch hole centered drill two 1 4 inch holes 2 inches apart Insert 2 No 8 plastic anchors into drilled holes b c Follow Figure 3 Temperature Control Panel for installation out side the steamroom 2 Attac...

Страница 8: ...o the control module Attach wires as shown in the blowup Figure 5 Check that all connections are made b c d in accordance with Wiring Diagram See Figure 7 e Replace control module cover D Steam Solenoid Valve There is no installation required for the steam solenoid valve it is factory installed and wired E Operation The temperature of the steambath is regu lated automatically by the ST 200CTempera...

Страница 9: ...PORTANT To check the function two lights are provided on the exterior of the System Control Module located on the steambath generator The Red Light indi cates there is electrical power to the Temperature Control Module The Green Light indicates the Steam Solenoid Valve is energized If a malfunction should occur in either the incom ing electrical power supply Red Light or the Steam Solenoid Valve G...

Страница 10: ... been generated from the boiler and the desired temperature reached in the steamroom the steam solenoid valve will close when controlled by the ST 200C The steamroom is now ready for use Note When the steam solenoid valve closes the red pilot light above the toggle switches will go out only after steam pressure builds to ap proximately 8 to 10 PSI within the boiler The boiler will maintain an 8 to...

Страница 11: ... a clear plastic dust cover TECHNICAL DATA Output 1 SPDT relay with dry contacts Switch Rating 16A 277VAC resistive 1 OOOW tungsten 240VAC 50OW 120VAC 1 2 hp 120VAC 1 hp 240VAC 100 hour capacitor back up of memory and display Supply voltages Separate Models 24VAC DC 120VAC 208 240VAC all 50 6OHz refer to product label Shortest switch time 1 minute Ambient Temperature Range 20 F to 140 F 28 C to 60...

Страница 12: ......

Страница 13: ......

Страница 14: ......

Отзывы: