background image

Holding down the Cycle key whilst applying power to the unit will cause all settings to revert to factory
default.

USE THIS FUNCTION WITH CAUTION 

as there is no way of reversing it. 

NOTE 

that this function will also clear any TFML module loaded.  

The input sub-menu is where the input to the unit is 
selected and configured.

Output configures the outputs of the unit. The format of
the output sub-menu varies according to the Output Pod
fitted. The two possible output types are:

1. Current transmission
2. Twin Relay

This sub-menu configures the units characteristics e.g.
communications and passcode.

If a TFML is loaded, this sub-menu gives access to the 8
TFML configuration registers.

tFnL

SyStEn

OUt  2

OUt  1

InPUt

FROM

RUN MODE

10.0 MENU MAP

11.0 RESETTING THE DEVICE

tYPE

Input type

rAnge

Range

Lin

Linearisation type

USEr  L

User Linearisation

uOLt

Voltage

rtd

RTD

tc

Thermocouple

CUrEnt

Current

10

±10 V

1

± 1 V

5

± 5 V

1.5

(± 1 to 5) V

4-2

20

(4 to 20) mA

20

(0 to 20) mA

10

(0 to 10) mA

0.1

± 100 mV

Displayed if voltage input is selected

Displayed if current input is selected

nOnE

None linear

S9rOOt

Square root

rOOt32

Power 3/2

rOOt52

Power 5/2

USEr

User defined

Ni  1  20

Ni120

CA

K

Current/Voltage

JISC

Pt100 USA/Japanese

USEr

User defined

RTD

J

J

t

T

r

R

S

S

E

E

F

F

n

N

b

B

USEr

User defined

Thermocouple

Pt100

Pt100 European

SE9ntS

Segments

EntEr

Enter

Enter value

In1

OUt1

Enter value

Enter value

dE9  C

Degree C

88888.8

1 DP

...Etc..

8.88888

5 DP

dE9  F

Degree F

ScALE

Scaling method

Eng  LO

Engineering low

Eng  HI

Engineering high

APPLy

Apply auto scale

Stndrd

Standard manual scaling applies

Auto

Auto scaling applies

Enter value

Enter value

FILtEr

Filter

Hi   

    LO

Enter value

Enter value

Apply electrical input low

Enter value

Apply electrical input high

dISPLY

Display variable

rAtE

Rate is displayed

tOtAl

Total is displayed

bOth

Both rate & Total are displayed

Enter value

Enter value

Enter value

Enter value

Enter value

SEcond

60  SEc

hour

12.0 INPUT MENU STRUCTURE

Page 13

Page 14

dEC  PL

Decimal place

UNItS

Temperature unit

bUrn

Burnout

InPUt

rESEt

Total reset value

di  UI  dr

Total divider

FActor

Total factor

t  bASe

Total time base

Lo  UAL

APL  Lo

HI  UAL

APL  HI

Содержание DM3600A

Страница 1: ...EVICE 13 12 0 INPUT MENU STRUCTURE 14 17 13 0 OUTPUT MENU STRUCTURE 18 20 14 0 SYSTEM MENU STRUCTURE 21 22 15 0 FAULT FINDING 23 Status Instruments Ltd Status Business Park Tewkesbury Glos GL20 8FD Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk 52 314 2358 02 Issue Web 4 DM3600A INDEX Single Channel Universal Input 6 Digit Indicator with Flow Totalizer Func...

Страница 2: ...on to an Installation over voltage Category II supply pollution degree 2 The supply voltage and frequency must remain within the limits stated on the product label The mains supply to the unit must be protected by an external 1 A fuse and a suitable switch or circuit breaker must be located close to the equipment in order to isolate the supply SIGNAL INPUT OUTPUTS All signal input and communicatio...

Страница 3: ...ert conductor tail sufficiently into 2 then release screwdriver Ensure no loose wire strands protrude Page 4 Power must be removed from unit before adding removing a pod Slot 1 alarm 1A and 1B should be positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator Slot 2 alarm 2A and 2B is positioned on the right To install an Option Pod slide back the...

Страница 4: ...ease contact your supplier When fitted this option provides the user with either 4 or 2 wire RS485 serial communications together two digital inputs Connections are made via a RJ45 connector A 0 5 m interface is supplied with this Page 5 Page 6 Material ABS PC Flammability IEC707 FV0 UL 94VO Weight 230 g Panel cut out 92 x 45 mm 1 2 3 4 5 R Load 1 2 3 4 5 V R Load Max RLoad 1 K 4 3 ISOLATED 4 TO 2...

Страница 5: ...stom 999 to 9999 Accuracy Linearisation Cold Junction Error Cold Junction Tracking Cold Junction Range 0 04 FS 0 04 reading or 0 5 C whichever is greater BS 4937 IEC 584 3 Custom 1 0 5 C 0 05 C C 20 to 60 C Thermal Drift Zero 4u V C Span 0 02 C Voltage Input Basic Accuracy 0 04 FS 0 04 of reading Thermal Drift 0 01 C Input Impedance 1 MΩ Linearity Linear X X3 2 X5 2 Custom Range 100m V 1 V 5 V 10 ...

Страница 6: ...BUS RTU protocol and can be configured using Status own M Config software Physical Layer 4 wire or 2 wire half duplex RS485 Protocol MODBUS RTU format Breakdown Isolation 500 VAC Maximum Fan out 32 units can be increased with repeaters Termination Standard RS485 The DM3600 is configured using the three keys on the front panel The unit has two modes of operation The first is Run mode This will auto...

Страница 7: ... If enabled this gives access to the relevant alarm setpoints To revert to Run mode press these keys up to 4 times Show electrical value e g 4 to 20 mA input Shows secondary value i e total or rate If enabled this will clear total and or latched alarms Perform clear function Show upper 6 digits of Total RUN MODE RATE OR TOTAL DISPLAYED Edit setpoints menu shortcut Followed by Enter menu mode 8 2 R...

Страница 8: ...1 100 mV Displayed if voltage input is selected Displayed if current input is selected nOnE None linear S9rOOt Square root rOOt32 Power 3 2 rOOt52 Power 5 2 USEr User defined Ni 1 20 Ni120 CA K Current Voltage JISC Pt100 USA Japanese USEr User defined RTD J J t T r R S S E E F F n N b B USEr User defined Thermocouple Pt100 Pt100 European SE9ntS Segments EntEr Enter Enter value In1 OUt1 Enter value...

Страница 9: ...s simply required to choose the tyPE and Lin linearity type For CurEnt or uOLt input types the user can choose STndrd or AUtO scaling from the ScALE sub menu 12 1 INPUT MENU BLOCKS SE9ntS In1 OUt1 In2 OUt2 ENGINEERING LOW HIGH If Stndrd scaling is chosen the user will encounter En9LO and En9HI entries in order to manually scale the input to the relevant input_lo and input_hi values see table overl...

Страница 10: ...factor and time base are used to scale the amount by which the total is incremented every second The total added every second is rate x factor time base x divider where time base is 160 or 3600 s The total displayed has a minimum number of 12 digits In normal running mode the 6 lower digits are shown by pressing the three front keys together the next 6 digits are shown RELAY OUTPUT MENU OUt 1 Outp...

Страница 11: ...required when the flow exceeds 10 000 kg h the setpoint will be set to 10 000 ALARM ACTION This defines the behaviour of the alarm when the setpoint is reached HYSTERISIS The hysterisis value is the difference between the points at which the alarm triggers and releases expressed in the relevant engineering units ALARM DELAY The alarm will not trigger until the PV has been in the alarm region for m...

Страница 12: ...m delay is 5 s and the maximum 3600 s DISCRETE ACTIVE LEVEL SELECT The function of the discrete input dISc is to operate as a remote clear button press i e you can use this to reset the totals remotely This menu item selects whether the clear function is executed when the discrete is high 24 V ACtHI or low 0 V ACtLO MENU ACCESS PASSCODE When accessing the menus from Run mode the user is prompted f...

Страница 13: ...IP CAL IS DISPLAYED The input calibrated data has been Re input calibration data If the error is corrupted still present replace the unit TOTAL DISPLAY AFTER Total has increased above the Press all three front panel keys together READING HIGH NOW displayed 6 low digits of the total and check the 6 high total digits SHOWS A LOW VALUE 15 0 FAULT FINDING Smart In Head Temperature Transmitters DIN Rai...

Отзывы: