RELAY SENSE

The ‘

Inurt

’ setting refers to the relay sense during powered operation. All other relay output menu 

settings refer to the alarm state. When in alarm, the relevant front panel LED is lit.

DEVIATION

If the ‘

dEu

’ action is chosen in the alarm action option, this value determines the amount by which the

PV may change before the alarm is triggered. The value should be in the engineering units.

This menu is only displayed if a current re-transmission output pod is fitted. If ‘

PrESEt

’ is chosen, the

output current can be edited in ‘

LEuEL

’. Otherwise, the re-transmitted current is derived linearly from

the process variable, using ‘

rEt LO

’ and ‘

rET HI

’.

RE-TRANSMISSION OUTPUT TYPE

The re-transmission can be set to represent rate or total.

SELECT OUTPUT SOURCE

The re-transmission can be set to represent rate or total.

OUTPUT SPAN

(4 to 20) mA, (0 to 20) mA or (0 to 10) mA can be selected as the span of the re-transmission.

RE-TRANSMISSION SCALE LOW / HIGH

By entering these values, the user can scale the mA output (selected in 

SPAn

) to the PV. Default values

will be equal to the engineering low and engineering high values entered in the input menu.

PRESET mA OUTPUT LEVEL

This is only available if ‘

PrESEt

’ output is chosen.

The relay menu shown is for alarm A. There are two alarms A and B so the menu will be duplicated for
alarm B. The relay menu will only be displayed if a twin relay pod is fitted to the DM3600.

SETPOINT A

The setpoint value defines the engineering value associated with an alarm. For example if an alarm is
required when the flow exceeds 10 000 kg/h, the setpoint will be set to 10 000.

ALARM ACTION

This defines the behaviour of the alarm when the setpoint is reached.

HYSTERISIS

The hysterisis value is the difference between the points at which the alarm triggers and releases,
expressed in the relevant engineering units.

ALARM DELAY

The alarm will not trigger until the PV has been in the alarm region for more than the specified number
of seconds.

LATCH

When latch is enabled, an alarm will remain triggered until it is manually cleared.

13.1 OUTPUT MENU FUNCTION BLOCKS

13.2 RELAY OUTPUT MENU

ALARM ACTION

ALARM BEHAVIOUR

OFF

(Off)

The alarm is always off

LO

(Low)

The alarm triggers when PV < setpoint, i.e. low alarm

HI

(High)

The alarm triggers when PV > setpoint, i.e. high alarm

dEu

(Deviation) The alarm triggers when PV moves out of a deviation band e.g. if the flow drops below 

or above the set point by 10 L/m.

tESt

(Test)

Alarm is on

AbOuE

(Above)

The alarm triggers when the total is > setpoint

bELOU

(Below)

The alarm triggers when the total is < setpoint

PULSE

(Pulse)

Alarm pulses when total is a multiple of setpoint i.e. if setpoint is set to 10, the 
alarm will pulse once every 10 units is added to the total. Pulse duration is 100 ms.

Not Triggered

Hysteresis

Hysteresis

Setpoint

PV

Alarm Function

Triggered

High Alarm

Low

Alarm

Setpoint

Deviation

Deviation

Deviation

Alarm

Alarm

Function

Not Triggered

Triggered

Hysteresis

Hysteresis

POWER ALARM STATUS

Inurt

SETTING RELAY POSITION (A) RELAY POSITION (B)

OFF

X

X

3 and 5

3 and 2

ON

Not in Alarm

nOnInu

3 and 4

3 and 1

ON

In Alarm

nOnInu

3 and 5

3 and 2

ON

Not in Alarm

InuErt

3 and 5

3 and 2

ON

In Alarm

InuErt

3 and 4

3 and 1

13.3 RE-TRANSMISSION (mA) OUTPUT MENU

Page 20

Page 19

Содержание DM3600A

Страница 1: ...EVICE 13 12 0 INPUT MENU STRUCTURE 14 17 13 0 OUTPUT MENU STRUCTURE 18 20 14 0 SYSTEM MENU STRUCTURE 21 22 15 0 FAULT FINDING 23 Status Instruments Ltd Status Business Park Tewkesbury Glos GL20 8FD Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk 52 314 2358 02 Issue Web 4 DM3600A INDEX Single Channel Universal Input 6 Digit Indicator with Flow Totalizer Func...

Страница 2: ...on to an Installation over voltage Category II supply pollution degree 2 The supply voltage and frequency must remain within the limits stated on the product label The mains supply to the unit must be protected by an external 1 A fuse and a suitable switch or circuit breaker must be located close to the equipment in order to isolate the supply SIGNAL INPUT OUTPUTS All signal input and communicatio...

Страница 3: ...ert conductor tail sufficiently into 2 then release screwdriver Ensure no loose wire strands protrude Page 4 Power must be removed from unit before adding removing a pod Slot 1 alarm 1A and 1B should be positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator Slot 2 alarm 2A and 2B is positioned on the right To install an Option Pod slide back the...

Страница 4: ...ease contact your supplier When fitted this option provides the user with either 4 or 2 wire RS485 serial communications together two digital inputs Connections are made via a RJ45 connector A 0 5 m interface is supplied with this Page 5 Page 6 Material ABS PC Flammability IEC707 FV0 UL 94VO Weight 230 g Panel cut out 92 x 45 mm 1 2 3 4 5 R Load 1 2 3 4 5 V R Load Max RLoad 1 K 4 3 ISOLATED 4 TO 2...

Страница 5: ...stom 999 to 9999 Accuracy Linearisation Cold Junction Error Cold Junction Tracking Cold Junction Range 0 04 FS 0 04 reading or 0 5 C whichever is greater BS 4937 IEC 584 3 Custom 1 0 5 C 0 05 C C 20 to 60 C Thermal Drift Zero 4u V C Span 0 02 C Voltage Input Basic Accuracy 0 04 FS 0 04 of reading Thermal Drift 0 01 C Input Impedance 1 MΩ Linearity Linear X X3 2 X5 2 Custom Range 100m V 1 V 5 V 10 ...

Страница 6: ...BUS RTU protocol and can be configured using Status own M Config software Physical Layer 4 wire or 2 wire half duplex RS485 Protocol MODBUS RTU format Breakdown Isolation 500 VAC Maximum Fan out 32 units can be increased with repeaters Termination Standard RS485 The DM3600 is configured using the three keys on the front panel The unit has two modes of operation The first is Run mode This will auto...

Страница 7: ... If enabled this gives access to the relevant alarm setpoints To revert to Run mode press these keys up to 4 times Show electrical value e g 4 to 20 mA input Shows secondary value i e total or rate If enabled this will clear total and or latched alarms Perform clear function Show upper 6 digits of Total RUN MODE RATE OR TOTAL DISPLAYED Edit setpoints menu shortcut Followed by Enter menu mode 8 2 R...

Страница 8: ...1 100 mV Displayed if voltage input is selected Displayed if current input is selected nOnE None linear S9rOOt Square root rOOt32 Power 3 2 rOOt52 Power 5 2 USEr User defined Ni 1 20 Ni120 CA K Current Voltage JISC Pt100 USA Japanese USEr User defined RTD J J t T r R S S E E F F n N b B USEr User defined Thermocouple Pt100 Pt100 European SE9ntS Segments EntEr Enter Enter value In1 OUt1 Enter value...

Страница 9: ...s simply required to choose the tyPE and Lin linearity type For CurEnt or uOLt input types the user can choose STndrd or AUtO scaling from the ScALE sub menu 12 1 INPUT MENU BLOCKS SE9ntS In1 OUt1 In2 OUt2 ENGINEERING LOW HIGH If Stndrd scaling is chosen the user will encounter En9LO and En9HI entries in order to manually scale the input to the relevant input_lo and input_hi values see table overl...

Страница 10: ...factor and time base are used to scale the amount by which the total is incremented every second The total added every second is rate x factor time base x divider where time base is 160 or 3600 s The total displayed has a minimum number of 12 digits In normal running mode the 6 lower digits are shown by pressing the three front keys together the next 6 digits are shown RELAY OUTPUT MENU OUt 1 Outp...

Страница 11: ...required when the flow exceeds 10 000 kg h the setpoint will be set to 10 000 ALARM ACTION This defines the behaviour of the alarm when the setpoint is reached HYSTERISIS The hysterisis value is the difference between the points at which the alarm triggers and releases expressed in the relevant engineering units ALARM DELAY The alarm will not trigger until the PV has been in the alarm region for m...

Страница 12: ...m delay is 5 s and the maximum 3600 s DISCRETE ACTIVE LEVEL SELECT The function of the discrete input dISc is to operate as a remote clear button press i e you can use this to reset the totals remotely This menu item selects whether the clear function is executed when the discrete is high 24 V ACtHI or low 0 V ACtLO MENU ACCESS PASSCODE When accessing the menus from Run mode the user is prompted f...

Страница 13: ...IP CAL IS DISPLAYED The input calibrated data has been Re input calibration data If the error is corrupted still present replace the unit TOTAL DISPLAY AFTER Total has increased above the Press all three front panel keys together READING HIGH NOW displayed 6 low digits of the total and check the 6 high total digits SHOWS A LOW VALUE 15 0 FAULT FINDING Smart In Head Temperature Transmitters DIN Rai...

Отзывы: