Servicing should only be performed by a Qualified Service Technician
•
Reinsert connector on Flame Sensor and make sure the electrical connection is clean and tight.
•
Recycle unit again to start another ignition cycle. If the burner ignites but the flame sense rod still fails
to detect flame, contact Commercial Technical Support.
BURNER DOES NOT IGNITE
Failure to ignite (no flame) usually means a gas supply or Gas Control Valve problem. If you do not see a
brief blue flame through the sight glass during the ignition cycle (at the moment the Gas Control Valve icon
appears on the display), follow these steps:
•
Remove and reinsert the Gas Control Valve electrical connector. Make sure the electrical connections
(pins) are clean and that the connector fits tightly.
VENTURI
LOW GAS
PRESSURE SWITCH
SUPPLY GAS
CONNECTION
GAS CONTROL
VALVE
COMBUSTION
AIR INLET
24 VAC SOLENOID
& WIRE HARNESS
GAS CONTROL VALVE ASSEMBLY: SUF 60120 - 100250 MODELS
LOW GAS
PRESSURE
SWITCH
SUPPLY GAS
CONNECTION
24 VAC SOLENOID
& WIRE HARNESS
GAS CONTROL VALVE ASSEMBLY: SUF 119300 - 119500 MODELS