Servicing should only be performed by a Qualified Service Technician
11. TEMPERATURE PROBE OPEN (UPPER OR LOWER)
CHANGE
BACK
ADVANCED
Lower Temp Probe (Open)
Fault occurred 0 mins ago
Lower Temperature Probe may be
open. Check connector and
resistance of Probe.
Press the Advanced button for
(press [DOWN] for more....)
CAUSES:
•
The Upper or Lower Temperature Probe appears
to be open (very high resistance). This fault code
often means the connector has been corroded by
cleaning chemicals or other substances.
CHECK/ REPAIR:
•
Make sure connector is clean and tight.
•
Check probe’s resistance.
•
Replace the Temperature Probe if open (resistance exceeds 56,000 Ohms). See Temperature Probe
section under "Temperature Probe Short (Upper or Lower)" section on Page 29.