Startco Engineering Ltd. 

Page 3 

 

SE-704 Earth-Leakage Monitor 

Rev. 2 

 
 

Pub. SE-704-M, January 18, 2008. 

2.3  F

RONT

-P

ANEL

 I

NDICATION

 

2.3.1  P

OWER

 

  The green LED labeled PWR indicates presence of 
supply voltage. 

 
2.3.2  T

RIP

 

  The red LED labeled TRIP indicates a trip.  A solid red 
LED indicates an earth-leakage trip and a flashing LED 
indicates a trip initiated by a CT fault.  Two fast flashes of 
the TRIP LED indicate a diagnostic trip.  See Section 2.5. 
 

2.3.3  CT V

ERIFICATION

 

  The green LED labeled CT indicates that an SE-CS30 
sensor is connected, even if CT verification is disabled. 
 

2.4  A

NALOG

 O

UTPUT

 

  The non-isolated, 0- to 5-V analog output indicates earth-
leakage current sensed by the earth-leakage CT.  The output 
is 5 V when earth-leakage current is 500 mA.  
 

2.5  S

ELF 

D

IAGNOSTICS

 

  A diagnostic trip is indicated by two fast flashes of the 
TRIP LED.  It can be caused by a problem detected by the 
watchdog timer, or from an incorrect reading from non-
volatile memory.  Press RESET or cycle supply voltage.  If 
the problem persists, consult Startco. 

3.  I

NSTALLATION

 

 This earth-leakage monitoring system consists of an 
SE-704 earth-leakage monitor and an SE-CS30 current 
sensor connected as shown in Fig. 2. 
  An SE-704 can be surface or DIN-rail mounted.  See 
Fig. 1.  Panel mounting requires a PMA-55 or PMA-60 
Panel-Mount Adapter.  See Figs. 5 and 6. 
  Pass the phase conductors through the CT window and 
position them in the centre of the opening (for 4-wire and 
single-phase systems, also pass the neutral conductor 
through the CT window).  Do not pass earth conductors 
through the CT window.  In applications that require 
shields or drain wires to pass through the CT window, 
return them through the CT window before connecting 
them to earth.  Connect an SE-CS30 current sensor to 
terminals 4 and 5, connect the shield to terminal 5, and 
earth terminal 5.  See Figs. 3 and 4 for SE-CS30 current-
sensor dimensional drawings. 
  Remove the connection to terminal 9 for dielectric-
strength testing. 
 

 
 

SE-CS30-X

S1 S2

STOP

START

1M

1M

SE-704

RS

REMOTE RESET

V

LEAKAGE

ANALOG

OUTPUT

O/L

L

N

4

5

13

14

15

16

6

7

8

9

L1

11

10

L2

N

ISOLATED CONTACTS

RESET

 

FIGURE 2.  Typical Connection Diagram 

Содержание SE-704

Страница 1: ...MONITOR PWR CT TRIP TEST RESET TIME ms 30 400 55 100 200 300 500 600 800 1000 10 LEVEL mA 150 30 60 80 200 300 400 500 100 STARTCO E N G I N E E R I N G L T D Copyright 2008 by Startco Engineering Ltd...

Страница 2: ...This page intentionally left blank...

Страница 3: ...Analog Output 3 2 5 Self Diagnostics 3 3 Installation 3 4 SE 704 Compatibility 4 5 Technical Specifications 9 6 Ordering Information 10 7 Warranty 10 8 Performance Test 11 LIST OF FIGURES PAGE 1 SE 70...

Страница 4: ...Startco Engineering Ltd Page ii SE 704 Earth Leakage Monitor Rev 0 Pub SE 704 M January 18 2008 This page intentionally left blank...

Страница 5: ...levels to be used by rejecting harmonics that can cause nuisance tripping The VARIABLE FREQUENCY setting uses a peak detection algorithm with a wider band width for fault detection in variable freque...

Страница 6: ...9 2 41 2 95 0 27 MOUNTING DETAIL NOTE 2 0 34 TOP OFF ON FIXED FREQUENCY VARIABLE FREQUENCY FAIL SAFE LATCHING NON FAIL SAFE AUTORESET 3 4 2 1 CONFIGURATION SWITCHES NOTES 1 DIMENSIONS IN MILLIMETRES...

Страница 7: ...cle supply voltage If the problem persists consult Startco 3 INSTALLATION This earth leakage monitoring system consists of an SE 704 earth leakage monitor and an SE CS30 current sensor connected as sh...

Страница 8: ...04 enclosure Both generations of SE 704 are compared in Table 1 The SE 704 was previously available with SE 704 01 120 Vac and SE 704 02 240 Vac control voltage options These have been discontinued An...

Страница 9: ...TING SCREWS M4 OR 8 32 68 0 26 0 52 5 5 0 5 0 68 0 34 0 26 5 25 0 58 0 17 0 26 5 72 0 110 0 MAX 52 5 42 6 2 68 1 02 2 07 0 20 0 20 2 68 1 34 1 04 0 98 2 28 0 67 1 04 2 83 0 43 2 07 1 68 M5 SCREWS TOP...

Страница 10: ...1 18 5 43 4 96 2 21 1 81 M5 SCREWS TOP MOUNTING DETAIL NOTE 3 FRONT SIDE 5 0 0 20 RECESSED FOR 8 mm HEX NUT 1 0 0 04 DEEP DETAIL A MOUNTING FOOT INSTALLATION TOOL NOTES 1 2 3 DIMENSIONS IN MILLIMETRES...

Страница 11: ...0 0 16 DIA 8 7 0 34 DIA 4 3 0 17 RAD 6 0 6 0 42 5 30 0 60 0 9 5 9 5 79 0 3 35 2 83 2 36 0 24 0 24 3 11 1 67 1 18 2 36 0 37 0 37 INSTALLATION INSTRUCTIONS NOTE PANEL CUTOUT DETAIL REMOVE BEZEL AND LAT...

Страница 12: ...LATCH MONITOR TO BRACKET INSERT BRACKET THROUGH FRONT OF PANEL CUTOUT AND SECURE WITH FLAT WASHERS AND LOCKNUTS PROVIDED CONNECTWIRINGTOTERMINALS ATTACH COVER USING THUMB SCREWS PROVIDED 1 2 3 4 1 DI...

Страница 13: ...ront Panel Switch and Remote N O Contact Functional Test Front Panel Switch Output Relay Contact Configuration Isolated N O and N C Operating Mode Fail Safe or Non Fail Safe CSA UL Rating 8 A Resistiv...

Страница 14: ...ORDERING INFORMATION SE 704 0 U Universal 120 240 Vac Vdc Supply D 12 24 Vdc Supply T 48 Vdc Supply 3 24 Vac Supply SE CS30 26 Current Sensor 26 0 mm 1 02 Window SE CS30 70 Current Sensor c w Flux Co...

Страница 15: ...f the circuit interrupting device in response to a simulated or controlled earth fault current To simulate earth fault current use CT primary current injection Fig 7 shows a test circuit using a Start...

Страница 16: ...Startco Engineering Ltd Page 12 SE 704 Earth Leakage Monitor Rev 0 Pub SE 704 M January 18 2008 This page intentionally left blank...

Отзывы: