Startco Engineering Ltd.
Page 10
SE-704 Earth-Leakage Monitor
Rev. 0
Pub. SE-704-M, January 18, 2008.
Fast
Transient....................IEC
61000-4-4, EN 61000-4-4
±
2 kV Common Mode
±
1 kV Differential Mode
Surge
Immunity.................IEC
61000-4-5, EN 61000-4-5
±
2.0 kV Common Mode
±
1.0 kV Differential Mode
Conducted
RF ...................IEC
61000-4-6, EN 61000-4-6
10Vrms, 0.15-80 MHz,
80% AM (1 kHz)
Magnetic
Field ..................IEC
61000-4-8, EN 61000-4-8
50 Hz, 30 A/m (continuous)
50 Hz, 300 A/m
(1 to 3 seconds)
Voltage
Interruption..........IEC
255-22-11, EN 60255-11
100% for 2, 5, 10, 20, 50,
100, & 200 ms
MHz
Burst.........................IEC
255-22-1, EN 60255-22-1
1 kV Differential Mode
2.5 kV Common Mode
RFI Compliance .....................FCC Part 15, Subpart B,
Class A – Unintentional
Radiators
Certification .............................. CSA (Canada and USA)
Australia
(1)
For earth-fault current in kA < 150 divided by the
trip setting in mA. [I
e
< (150/level) x 1,000 A]
(2)
At 50 or 60 Hz.
(3)
SE-CS30-series CT included.
(4)
Maximum lead resistance of 2
Ω
.
(5)
Trip Time at 3 x trip-level setting.
6. O
RDERING
I
NFORMATION
SE-704-0
U Universal 120/240-Vac/Vdc Supply
D
12/24-Vdc
Supply
T
48-Vdc
Supply
3
24-Vac
Supply
SE-CS30-26 .........Current Sensor,
26.0 mm (1.02”) Window
SE-CS30-70 .........Current Sensor c/w Flux Conditioner,
69.8 mm (2.75”) Window
PMA-55 ...............Panel-Mount Adapter, NEMA 1
PMA-60 ...............Panel-Mount Adapter, NEMA 3, IP53
PMA-3..................Adapter Plate, GEC/MCGG
PMA-6..................Adapter Plate, FPL-GFRM
PMA-15 ...............Adapter Plate, MGFR
Consult factory for custom mounting adapters.
7.
W
ARRANTY
The SE-704 Earth-Leakage Monitor is warranted to be
free from defects in material and workmanship for a
period of five years from the date of purchase.
Startco Engineering Ltd. will (at Startco’s option)
repair, replace, or refund the original purchase price of
an SE-704 that is determined by Startco to be defective if
it is returned to the Startco factory, freight prepaid,
within the warranty period. This warranty does not
apply to repairs required as a result of misuse,
negligence, an accident, improper installation,
tampering, or insufficient care. Startco Engineering Ltd.
does not warrant products repaired or modified by non-
Startco Engineering Ltd. personnel.
Содержание SE-704