LOW AMBIENT OPERATION CHARGE
Some Master-Bilt
®
units are provided with condenser flooding valves to maintain proper head pressure during the winter.
These valves function by reducing the effective condenser area by flooding or “backing up” refrigerant in the condenser to
reduce the amount of surface available for condensing. To operate properly, more charge is required during this flooding
condition. These flooding valves are standard on “B” models and optional on others.
To use the charts, multiply the number in Chart B by the percent flooding required in Chart C to arrive at the additional charge
required after providing a clear sight glass.
Example: Determine the additional charge required to operate a BCHX0750 at +20°F suction if the unit is charged at +50°F.
From Chart B, model BCHX0750 has a condenser internal volume of 26.3 lbs. of refrigerant. From Chart C at +50°F at time
of charging and +20°F suction, the condenser would need to be flooded 32%.
Therefore, multiply 26.3 lbs. x 32% = 8.4 lbs. to arrive at the additional charge that must be added after clearing the sight glass
for proper winter operation.
CONDENSER VOLUME IN LBS.
Chart B
Lbs. of
Lbs. of
Lbs. of
Lbs. of
Lbs. of
Lbs. of
Charge
Charge
Charge
Charge
Charge
Charge
Unit
to Fill
to Fill
Unit
to Fill
to Fill
Unit
to Fill
to Fill
Model
(R-22)
(R-404A)
Model
(R-22)
(R-404A)
Model
(R-22)
(R-404A)
BCH*0300
8.4
7.1
BHMX0300
8.4
MCHX0060
4.2
BCH*0500
13.6
13.2
BHMX0400
13.6
MCHX0080
4.2
BCH*0750
26.3
25.6
BHMX0500
13.6
MCHX0110
4.2
BCH*1000
38.8
37.8
BSLZ0300
5.3
MCHX0150
7.9
BCH*1500
38.8
37.8
BSLZ0350
5.3
MCHX0190
7.9
BCHX0150
5.8
BSLZ0400
7.1
MCHX0300
10.2
BCHX0200
5.4
BSLZ0500
7.1
MCHX0440
25.0
BCLZ0150
5.7
BSLZ0600
13.2
MCHX0500
25.0
BCLZ0170
5.7
BSLZ0750
13.2
MCLZ0020
4.1
BCLZ0200
5.7
MCLZ0030
4.1
BCLZ0250
5.3
MCLZ0050
4.1
BCLZ0280
7.1
MCLZ0070
4.1
BCLZ0300
7.1
MCLZ0100
7.7
BCLZ0400
7.1
MCLZ0140
7.7
BCLZ0600
13.2
MCLZ0170
10.0
BCLZ0750
20.9
MHHX0060
4.2
BCLZ0900
25.6
MHHX0080
4.2
BCLZ1000
25.6
MHHX0110
4.2
BCLZ1500
37.8
MHHX0120
7.9
BCLZ2200
37.8
MHHX0150
7.9
BCM*0150
5.8
5.7
MHHX0190
7.9
BCM*0200
5.4
5.3
MHHX0250
7.9
BCM*0300
8.4
7.1
MHHX0300
10.2
BCM*0500
13.6
13.2
MHHX0350
10.2
BCM*0750
21.4
20.9
MHHX0440
25.0
BCM*1000
26.3
25.6
MHHX0500
25.0
BCM*1500
38.8
37.8
MHLZ0020
4.1
BCM*2000
38.8
37.8
MHLZ0030
4.1
BCMX0070
N/A
N/A
MHLZ0050
4.1
BCMX0100
N/A
N/A
MHLZ0070
4.1
BHH*0200
5.4
5.3
MHLZ0090
7.7
BHH*0250
5.4
5.3
MHLZ0120
7.7
BHH*0300
8.4
7.1
MSLZ0070
4.1
BHH*0400
13.6
13.2
MSLZ0100
7.7
BHH*0500
13.6
13.2
MSLZ0150
7.7
BHMX0200
5.4
MSLZ0180
24.3
BHMX0250
5.4
MSLZ0220
24.3
*Unit can be filled with either R-22 or R-404A refrigerant
Содержание BCHX0050B
Страница 17: ...5 16 Rev B 57 02497 NOTE Sizes specified are for Type L copper tubing...
Страница 18: ...5 16 Rev B 57 02497 18 NOTE Sizes specified are for Type L copper tubing...
Страница 21: ...5 16 Rev B 57 02497 21...
Страница 40: ...5 16 Rev B 57 02497 40 UNIT BASE SPECIFICATIONS...
Страница 41: ...5 16 Rev B 57 02497 41 UNIT BASE SPECIFICATIONS CONT...
Страница 42: ...5 16 Rev B 57 02497 42 UNIT BASE SPECIFICATIONS CONT...