EQUIVALENT LENGTH ALLOWANCE FOR FITTINGS
EQUIVALENT LENGTH IN FEET
FITTING
90°
45°
Tee
Tee
SIZE
Ell
Ell
(Line)
(Branch)
1/2"
.9
.4
.8
2.0
5/8"
1.0
.5
1.0
2.5
7/8"
1.5
.7
1.5
3.5
1-1/8"
1.8
.9
1.5
4.5
1-3/8"
2.4
1.2
1.8
6.0
1-5/8"
2.8
1.4
2.0
7.0
2-1/8"
3.9
1.8
3.8
10.0
Chart A
GENERAL:
1.
Suction lines should be pitched down in direction of flow, 1/2" per 10 feet of line.
2.
Refrigerant lines should be supported and fastened properly to prevent leaks and for
professional looking installation. Supports should be every 5 feet for lines to 7/8" OD, 7 feet
for 1-1/8" to 1-3/8" OD lines, and 10 feet for 1-5/8" and 2-1/8" OD lines.
3.
Where condensation dripping would be objectionable, insulate suction lines, and where the sun
could adversely affect performance, insulate both the liquid and suction lines. Insulation
thickness of 1/2" will usually be adequate.
4.
A “P” trap must be installed at the bottom of the riser in all vertical suction lines rising 4" or
more. To insure proper oil return to the condensing unit, the trap should be the same size as the
horizontal line and the riser should be sized per the line sizing charts on pages 14-17.
In installations where condensate can accumulate on the vibrasorber, a covering of heat shrink
PVC tubing or waterproof tape may be used to prevent freezing under the ferrule, causing a
rupture
.
Содержание BCHX0050B
Страница 17: ...5 16 Rev B 57 02497 NOTE Sizes specified are for Type L copper tubing...
Страница 18: ...5 16 Rev B 57 02497 18 NOTE Sizes specified are for Type L copper tubing...
Страница 21: ...5 16 Rev B 57 02497 21...
Страница 40: ...5 16 Rev B 57 02497 40 UNIT BASE SPECIFICATIONS...
Страница 41: ...5 16 Rev B 57 02497 41 UNIT BASE SPECIFICATIONS CONT...
Страница 42: ...5 16 Rev B 57 02497 42 UNIT BASE SPECIFICATIONS CONT...