![Stahl SolConeX Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/stahl/solconex/solconex_operating-instructions-manual_1357585045.webp)
205582 / 8581615300
2020-08-27·BA00·III·en·05
Maintenance, Overhaul, Repair
21
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
SolConeX Wall-mounting socket, 125 A
Series 8581/31
9.1
Padlocking with a Padlock
10
Maintenance, Overhaul, Repair
10.1 Maintenance
• Consult the relevant national regulations to determine the type and extent of
inspections.
• Adapt inspection intervals to the operating conditions.
At a minimum, check the following points during maintenance work on the device:
• Firm fit of the conductors,
• Damage on the enclosure, seals or surface,
• Dirt on the sleeves,
• Compliance with the permissible temperatures (according to IEC/EN 60079),
• Whether the device is used in accordance with its intended use.
10.2 Overhaul
The rotary actuator for switching the socket can be locked with a padlock
(max. bracket diameter of 8 mm) in 0 or I positions.
DANGER
Overheating and explosion hazard due to defective switching contacts!
Non-compliance results in severe or fatal injuries.
• Replace the entire socket flange after each short circuit in the
main circuit of the switch because the state of the switching
contacts cannot be checked in hermetically sealed equipment.
Observe the relevant national regulations in the country of use.